Terminals; Parameter List - Mitsubishi Electric FR-A7AR Instruction Manual

Hide thumbs Also See for FR-A7AR:
Table of Contents

Advertisement

RELAY OUTPUT

3.2 Terminals

2A
1A
2B
1B
2C
1C
3A
3B
3C
*The operation of each relay depends on the output signal selected.

3.3 Parameter List

By installing this plug-in option, the parameters below are extended.
Set the values according to need.
Parameter Number
320
321
322
Use Pr. 320 to Pr. 322 to select signals used for relay output. (Refer to page 11 for signal types.)
REMARKS
⋅ For Pr.320 to Pr.322, write is disabled during operation even when "2" is set in Pr.77 Parameter write selection.
When changing the parameter setting, stop the operation.
⋅ When an option alarm (
10
Terminal Symbol
1A
1B
1C
2A
2B
2C
3A
3B
3C
Name
RA1 output selection
RA2 output selection
RA3 output selection
) occurs, all outputs are tuned off.
Description
Relay RA1's normally open contact terminal
Relay RA1's normally closed contact terminal
Relay RA1's contact common terminal
Relay RA2's normally open contact terminal
Relay RA2's normally closed contact terminal
Relay RA2's contact common terminal
Relay RA3's normally open contact terminal
Relay RA3's normally closed contact terminal
Relay RA3's contact common terminal
Setting Range
0 to 5, (7), 8, 10 to 19, 25, 26, 45
to 47, 64, 70, (71 to 78), 86 to 91,
94 to 96, 98, 99, 9999
Initial Value
0
1
2