Terminals - Mitsubishi Electric 800 Series Instruction Manual

Inverter plug-in option
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

3.2

Terminals

• FR-A8AX
X0
X1
X2
X10
X3
X11
X4
X12
X5
X13
X6
X14
X7
X15
X8
DY
X9
Terminal
Terminal
location
symbol
Digital signal input terminal (frequency setting / torque command signal terminal
Input the digital signal at the relay contact or open collector terminal. (Refer to
X0 to X15
For the digital signal input, choose either BCD code or binary.
BCD code input is 3-digit (999 maximum) or 4-digit (9999 maximum).
Built-in
Binary input is 12-bit (X0 to X11, HFFF maximum) or 16-bit (X0 to X15, HFFFF maximum).
option
Data read timing input signal.
Use when a digital signal read timing signal is necessary. When Pr.305 Read timing operation selection = "1",
DY
data is read only while the DY signal is ON. In addition, the X0 to X15 data before the signal is turned OFF is
retained by turning OFF the DY signal. (Refer to
Common terminal (sink).
SD
Common terminal for digital and data read timing signals.
Use terminal SD of the inverter.
Inverter
External transistor common (sink), common terminal (source).
Connect this terminal to the external power supply common terminal (+) of a transistor output (open collector
PC
output) device, such as a programmable controller, to avoid malfunction by undesirable current. When the
source logic is selected, this terminal is used as a common terminal. Use terminal PC of the inverter.
*1
Torque command values can be input to the FR-A800 series only.
Description
*1
page
page
25.)
16-BIT DIGITAL INPUT
).
19.)
21