Parameter Setting Examples - Acs850 And Acq810; Speed Control Using The Profidrive Communication; Profile With Ppo Type 4 - ABB FENA-01 User Manual

Ethernet adapter module
Hide thumbs Also See for FENA-01:
Table of Contents

Advertisement

280 PROFINET IO – Start-up
7. Define the process data transferred to and from the drive in
parameter groups 52 and 53.
Note: The adapter module automatically sets the
communication profile-specific virtual address for the Status
word in parameter 52.01 and for the Control word in parameter
53.01.
8. Validate the settings made in parameter groups 51, 52 and 53
with parameter 51.27 FBA par refresh.
9. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Parameter setting examples – ACS850 and ACQ810

Speed control using the PROFIdrive communication

profile with PPO Type 4

This example shows how to configure a basic speed control
application that uses the PROFIdrive profile. In addition, some
application-specific data is added to the communication.
The start/stop commands and reference are according to the
PROFIdrive profile, speed control mode. For more information, see
the PROFIdrive state machine on page 312.
The reference value ±16384 (4000h) corresponds to parameter
19.01 Speed scaling in the forward and reverse directions.
Direction
PZD1
Out
Control
word
In
Status
word
1)
Example
PZD2
PZD3
Speed
Constant speed 1
reference
Speed Actual
Power
value
PZD4
PZD5
1)
Constant speed 2
1)
DC bus voltage
PZD6
1)
1)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fena-11Fena-21

Table of Contents