WI742D 5/03
Connecting 2-wire smoke detectors to zones 1-6
Wiring diagram, 4-wire smoke detectors
Additional 4-wire smokes
Sound Alarm On Exit Error (SIA CP-01 Requirement: 4.2.2.4)
An Exit Error sequence is initiated if an entry/exit zone is violated at the expiration of the Exit Time. An Exit Error is processed
as follows:
1. The local alarm shall immediately sound.
2. The keypad annunciator sounds an Entry Delay.
3. An Entry Delay is initiated.
4. If the alarm system is not Disarmed at the end of the Entry Delay, the Alarm Transmission Sequence is initiated.
5. The Alarm Transmission includes the alarm and an Exit Error.
Split Reporting See Report Telco 3
Start Exit Delay After Ringback
When a closing report is successfully received, the central station will acknowledge by returning a kissoff signal. When the kis-
soff is received by the communicator, a 2-second ringback tone will sound at the keypad. Start Exit Delay After Ringback will cause
the exit delay to start after the ringback sounds.
L
NAPCO Security Systems
ZONE
RESISTOR
LOCATION ON BOARD
1
R1
ABOVE TERMINAL 18
2
R2
ABOVE TERMINAL 18/19
3
R3
ABOVE TERMINAL 19
4
R4
ABOVE TERMINAL 20
5
R5
ABOVE TERMINAL 22
6
R6
ABOVE TERMINAL 23
Four-Wire Smoke Detectors.
smokes, subtract smoke-detector alarm current from
available standby current.
LISTED DEVICES.
Wire 4-wire smokes as shown in the following wiring dia-
gram. Program each zone for Fire. Also program zones
for Pulse Burglary Output, and Disable Fire Reset in the
applicable area(s) (System Options). If they are of the
self-resetting type, 4-wire smokes may be powered from
Terminals 13 and 14 (AUX. PWR.) instead of Terminal 28
and 29, thus freeing the Reset Relay for other uses.
X
GEM-P9600 Installation Instructions
!
Page 47
If installing 4-wire
See COMPATIBLE UL-