RF Jam Reporting
RF Receiver Jam will report as RF Receiver Trouble.
Second Call Answering Machine Override
If using the PCD-Windows PC downloader Software, the Telco Answering Service can now be disabled. Call the panel, hang up
after one ring by pressing the F10 key. The PCD-Windows will automatically call the panel back and the panel will answer in one
ring. See Callback-Method Download for more information.
Selective Bypass
Disable Code Required for Easy Bypass (Not for UL installations.)
Any or all zones (1–96) programmed for Selective Bypass may be removed from the system, but each must be removed sepa-
rately. Refer to BYPASSING ZONES in Section 3 for operation. Security Bypass: Recommended for commercial applications, re-
quires entry of a valid user code. Easy Bypass: Recommended for residential applications, is selected by programming Disable
Code Entry for Easy Bypass; this will permit bypassing/unbypassing zones without the need of entering a code (see Easy Bypass in
Section 3). Do not program this feature in high-security applications. When one or more zones is bypassed, the "BYPASSED" reminder
on the GEM-RP1CAe2 and GEM-K1CA keypads will display.
Sensor Watch
Program for any zone containing a PIR or dual-technology sensor, floor mats, door contacts, or other device where some activity
is expected. This feature supervises the sensor by verifying that the zone activates before the PIR timer runs out. If no trip is de-
tected within the programmed Sensor-Watch time, a system trouble will result and "E22-NN PIR SENSOR TRBL" will be displayed at the key-
pad, where NN are the zone number(s). Select the RESET SENSOR MSG function to reset this system trouble.
Program the Sensor-Watch PIR timer in Location 4088. Select a value in accordance with the anticipated activity within the cov-
erage area while disarmed. In calculating the Sensor-Watch time, note that only the disarmed hours (the time between armed peri-
ods) are added. In moderate traffic areas, a Sensor-Watch time of perhaps 1 hour may be appropriate, whereas in remote areas, a
time of 8 hours or more may be in order. Supervision time should be calculated for the supervised zone with the least amount of traf-
fic. Up to 255 hours may be programmed (see Time Selection).
Silence All Outputs During Audio Session See Veri-Phone
Silence All Outputs During Audio Session with Lug E19
Whenever an active low is applied to control-panel Lug E19 (Listen-In), all output relays will turn off. Connect Veri-Phone Termi-
nal 16 (INHO) to Lug E19.
Single-Digit Format See Data Format
Smoke Detectors
Connect smoke detectors as shown in the following diagrams. The normally-closed contacts of the Reset Relay are used to re-
Connecting 2-wire smoke detectors to zones 7 & 8
X
GEM-P9600 Installation Instructions
set the smoke detectors.
Two-Wire Smoke Detectors: Use Zones 7 and 8.
Zones 7 and 8 have been designed so they can be easily
configured as 2-wire smoke detector zones by means of
jumpers (JP7) located above Terminal 21.
1.
If Zone 7 is selected as a 2-Wire Fire Zone, move the left
jumper on JP7 from the top two pins (BURG) to the bottom
two pins (2WF).
2.
Similarly, if Zone 8 is selected as a 2-Wire Fire Zone, move
the right jumper on JP7 from the top two pins (BURG) to the
bottom two pins (2WF).
3.
Connect 2-wire smoke detectors to Zones 7 and/or 8 as
shown.
Two-Wire Smoke Detectors: Use Zones 1-6.
Additionally, where more than two 2-wire smoke detector zones
are required, select any of Zones 1–6 for 2-wire fire as fol-
lows:
1.
Program the selected zone(s) (1–6) for 2-Wire Smoke Detec-
tors and Fire.
2.
Cut out the 2700Ω resistor (color code: red/violet/red) associ-
ated with the selected zone(s). See table below.
3.
Install a 130Ω resistor across the 2 terminals of each zone
used (color code: brown/orange/brown).
4.
Wire positive (+) terminal of smoke detector to terminal 28.
Wire negative (-) terminal of smoke detector to positive (+)
terminal of the zone.
L
WI742D 5/03
NAPCO Security Systems