Fuel System Requirements And Recommendations; Battery Installation - Generac Power Systems 13694330200 Owner's Manual

Stationary emergency generator
Table of Contents

Advertisement

General Information
BLACK
___________
RED LEAD
(FROM STARTER
CONTACTOR)
BLACK LEAD
~
(FROM FRAME)
---<~~
+
BATTERY
4.
Connect the red battery cable (from starter contactor) to the
battery post indicated by a positive,
pas
or
(+).
5.
Connect the black battery cable (from frame ground) to the
battery post indicated by a negative, NEG or (-).
NOTE:
Damage will result if battery connections are made in reverse.
NOTE:
The generator is equipped with a battery trickle charger that is
active when the unit is set up for automatic operation. With the
battery installed and utility power source voltage available, the
battery receives a trickle charge while the engine is not run-
ning, to prevent self-discharge. The trickle charger is designed
to help extend the life of the battery by maintaining the battery
when the unit is not running. The trickle charge feature cannot
be used to recharge a discharged battery.
Before installing and connecting the battery, complete the follow-
ing steps:
1.
Set the generator's AUTO/OFF/MANUAL switch to OFF.
2.
Turn off utility power supply to the transfer switch.
3.
Remove the 10A and 15A fuses from the generator control
panel.
Battery cables were factory connected at the generator (Figure
1.4). Connect cables to battery posts as follows:
Figure 1.4 - Battery Cable Connections
Diesel Engine
Battery Size
Minimum CCA
2.4L
3.4L
GRP 27 or GRP 31
650 or 925
4.5L
GRP 31 or GRP
925
31E
6.7L (100, 130Kw)
1 or 2 X GRP 31
925
6.7L (150, 175Kw)
2 X GRP 31
925
8.7L
10.3L
12.9L
13.0L
2 x GRP 31 or 2 x
16.0L
GRP 80
925 or 1155
18.0L
22.0L
Fill the battery with the proper electrolyte fluid if necessary and
have the battery fUlly charged before installing it.
BATTERY INSTALLATION
When a unit is supplied with out a battery or during replacement
use the following table to properly select the battery size and mini-
mum Cold Cranking Ampere required for a particular unit.
FUEL SYSTEM REDUIREMENTS AND RECOMMENDATIONS
Diesel Fuel System: See Chapter 8 of Engine-Generator Stationary
Emergency Electric Power Systems Installer's Guide and Reference
Manual (part no. 046622).
1.
Beginning October 1, 2007, owners and operators that use
diesel fuel must use diesel fuel that meets:
A. Sulfur content of 500 parts per million (ppm) maximum.
B. Cetane index or aromatic content as follows:
• A minimum cetane index of 40 or;
• A maximum aromatic content of 35 volume percent.
2.
Beginning October 1, 2010, owners and operators that use
diesel fuel must use diesel fuel that meets:
A. Sulfur content of 15 parts per million (ppm) maximum.
B. Cetane index or aromatic content as follows:
• A minimum cetane index of 40 or;
• A maximum aromatic content of 35 volume percent.
7