Maintenance
Maint
Maintenance
Maintenance Tasks
Task Completed
Level
Interval
Date/Initials
1. Disable the unit from operating per the first page warning.
2.
Check the engine oil level. Adjust as necessary.
3. Check the engine coolant level. Adjust as necessary.
4.
Check the battery electrolyte level if accessible. Adjust as
necessary.
Every 6 months
or
5.
Check the diesel fuel supply level. Adjust as necessary.
50 hours of
operation
2
6. Drain water and sediment from the diesel fuel tank.
(Requires
approximately
7.
Drain water from the diesel fuel line water separator if unit is equipped
1.5 man hours
with one.
per unit)
8.
Check the air inlets and outlets for debris. Clean as necessary.
9. Visually inspect the unit looking for leaks, wear or damage, loose con-
nections or components, and corrosion. Correct as necessary.
10. Initiate an automatic start and transfer to load of the unit, and exer-
cise it for at least 1 hour looking for leaks, loose connections or com-
ponents, and abnormal operating conditions. Correct as necessary.
11. Return the unit to standby setup for operation when required.
Technician's Signature
Date Inspection Completed
Unit Hour Meter Reading at Completion of the Inspection
23