Maintenance
Maint
Maintenance
Maintenance Tasks
Task Completed
Level
Interval
Date/lnitials
1.
Disable the unit from operating per the first page warning.
2. Check the engine oil level. Adjust as necessary.
3, Check the engine coolant level. Adjust as necessary,
4, Check the battery electrolyte level if accessible, Adjust as necessary,
5, Check the diesel fuel supply level. Adjust as necessary.
First 6 months
6, Drain water and sediment from the diesel fuel tank.
or
50 hours of
operation
7. Drain water from the diesel fuel line water separator if unit is equipped
ONLY
with one,
1A
8, Check the air inlets and outlets for debris, Clean as necessary,
(Requires
approximately
2,5 man hours
g, Visually inspect the unit looking for leaks, wear or damage, loose
per unit)
connections or components, and corrosion, Correct as necessary,
1O, Initiate an automatic start and transfer to load of the unit, and exercise it
for at least 1 hour looking for leaks, loose connections or components,
and abnormal operating conditions, Correct as necessary,
11, Change the engine oil.
12, Replace the engine oil
13. Replace the engine fuel filter(s),
14, Return the unit to stand-by setup for operation when required,
Technician's Signature
Date Inspection Completed
Unit Hour Meter Reading at Completion of the Inspection