Electrical Requirements for Electric
Models
Refer to Table 6.
NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code for 75°C Conductors
and are intended for use as a guideline only.
Electrical connections should be made only by a
qualified electrical contractor in accordance with
all applicable local and national requirements.
For 21 kW T30 Electric Models:
Serial Plate
Voltage
200-208V/60Hz/3ph*
200V/50Hz/3ph*
230-240V/50Hz/3ph*
240V/60Hz/3ph*
380V/50 or 60Hz/3ph*
400-415V/50Hz/3ph*
460-480V/60Hz/3ph*
* These serial plate voltages are only options available on the T30 electric models. Current (Amp) is for one pocket only.
** Per heater on T30 electric models, each has two heaters.
4-08-43
Terminal Block
Current
Connections
(Amps)
Required
L1, L2, L3,
and ground
L1, L2, L3,
and ground
L1, L2, L3,
and ground
L1, L2, L3,
and ground
L1, L2, L3,
and ground
L1, L2, L3,
and ground
L1, L2, L3,
and ground
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of "single
phasing" and causing premature failure of the
motor(s).
Recommended
Breaker Rating
(Amps)
62**
80
60**
80
55**
70
54**
70
33**
45
31**
40
27**
35
Table 6
Tumblers – T30 and T45
Recommended
Breaker
Minimum
Poles
Conductor Size
(AWG [mm
3
4 (21.2)
3
4 (21.2)
3
4 (21.2)
3
4 (21.2)
3
8 (8.37)
3
8 (8.37)
3
8 (8.37)
2
])
20