And 75 Pound Electric Models - IPSO TMB795C Planning Manual

50 and 75 pound tumblers on-premise laundry planning handbook
Table of Contents

Advertisement

50 and 75 Pound Electric Models

Refer to Table 6.
NOTE: Wire size and breaker ratings were
obtained from the Canadian Electrical Code for
75 C. wire and are intended for use as a guideline
only. Electrical connections should be made by a
qualified electrical contractor in accordance with
all applicable local and national requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
Serial Plate Rating
240V/50Hz/1ph
(50 Pound only)
200-208V/60Hz/3ph
200V/50Hz/3ph
230V/50Hz/3ph
240V/50Hz/3ph
240V/60Hz/3ph
380V/50 or 60Hz/3ph
400-415V/50Hz/3ph
440V/60Hz/3ph
480V/60Hz/3ph
4-08-44
Terminal Block
Connections
Required
L1, Neutral and Ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of "single
phasing" and causing premature failure of the
motor(s).
Serial Plate Amps
Nonreversing
Reversing
93
95
89
88
84
85
73
75
79
78
79
78
47
48
43
44
41
41
38
38
Table 6
Tumblers – 50 and 75
Recommended Circuit
Wire Size
Breaker
Rating
AWG (mm
125A – 1 pole
1 (42.4)
125A – 3 pole
1 (42.4)
125A – 3 pole
1 (42.4)
100A – 3 pole
3 (26.7)
100A – 3 pole
3 (26.7)
100A – 3 pole
3 (26.7)
60A – 3 pole
6 (13.3)
60A – 3 pole
6 (13.3)
51A – 3 pole
6 (13.3)
50A – 3 pole
6 (13.3)
2
)
20