Electrical Requirements - IPSO 170 Planning Manual

120 and 170 pound tumblers
Table of Contents

Advertisement

Tumblers – 120 and 170

Electrical Requirements

Refer to Table 5.
NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should be
made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
For 120 Pound Tumbler Models
Serial Plate Rating
208-230V/60Hz/3ph
380-415V/50Hz/3ph
380V/60Hz/3ph
440V/60Hz/3ph
460-480V/60Hz/3ph
* Current ratings vary slightly depending on model; refer to serial plate.
For 170 Pound Tumbler Models
Serial Plate Rating
208-230V/60Hz/3ph
380-415V/50Hz/3ph
380V/60Hz/3ph
440V/60Hz/3ph
460-480V/60Hz/3ph
* Current ratings vary slightly depending on model; refer to serial plate.
17
Terminal Block
Connections Required
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
Terminal Block
Connections Required
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
L1, L2, L3 and ground
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: 3 Phase Only– Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of "single
phasing" and causing premature failure of the
motor(s).
Rated
Breaker
Current*
Rating
7.7
15 Amps
3.8
10 Amps
4.1
10 Amps
3.8
10 Amps
3.9
10 Amps
Rated
Breaker
Current*
Rating
13.5
20 Amps
6.9
15 Amps
6.6
15 Amps
6.4
15 Amps
6.7
15 Amps
Table 5
Breaker
Recommended
Poles
Wire Size
3
14 AWG (2.08 mm
3
14 AWG (2.08 mm
3
14 AWG (2.08 mm
3
14 AWG (2.08 mm
3
14 AWG (2.08 mm
Breaker
Recommended
Poles
Wire Size
3
12 AWG (3.31 mm
3
14 AWG (2.08 mm
3
14 AWG (2.08 mm
3
14 AWG (2.08 mm
3
14 AWG (2.08 mm
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)