120 and 170 Pound Tumblers
Refer to Installation manual for full instructions.
3-09-71R6
October 2011
On-Premise
Starting Serial No. 0907003062
Laundry
Planning
Handbook
TMB1268C
TMB1268C

Advertisement

Table of Contents
loading

Summary of Contents for IPSO TMB1268C

  • Page 1 120 and 170 Pound Tumblers Refer to Installation manual for full instructions. 3-09-71R6 October 2011 On-Premise Planning Handbook Starting Serial No. 0907003062 Laundry TMB1268C TMB1268C...
  • Page 2: Table Of Contents

    Table of Contents © Published by permission of the copyright owner. All rights reserved. No part of the contents of this book may be reproduced or transmitted in any form or by any means without the expressed written consent of the publisher. ©...
  • Page 3: Tumblers - 120 And 170

    RD – reversing DMP OPL © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT 3-09-71 Steam/Thermal Oil IPD120G2-IT120N IPD120S2-IT120S IPD170G2-IT170N IPD170S2-IT170S RE – reversing LED OPL TMB1268C Electric IPD120S2-IT120T IPD120E2-IT120E IPD170S2-IT170T RQ – reversing dual digital timer TMB1268C...
  • Page 4 Tumblers – 120 and 170 120 POUND TUMBLER Serial Plate Multiply 0.252 1055 Inch 25.4 Inches W.C. 0.036 Inches W.C. 0.249 lb./inch (psi) 6.895 28.32 © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT Conversion Table To Obtain Multiply kCal Pounds/sq.
  • Page 5: Specifications And Dimensions

    Specifications and Dimensions Specifications Noise level measured during operation at operator position of 3.3 feet (1 meter) in front of machine and 5.2 feet (1.6 meters) from floor. Cylinder Size: Inches (mm) Cylinder Capacity dry weight: Pounds (kg) Cylinder Motor Horsepower Fan Motor Horsepower Air Outlet Diameter: Inches (mm)
  • Page 6: 120 Pound Tumbler Dimensions And Exhaust Outlet Locations

    Tumblers – 120 and 170 120 Pound Tumbler Dimensions and Exhaust Outlet Locations Models 31.38 in. 32.5 in. 120L/N/E (797 mm) (826 mm) 31.38 in. 32.5 in. 120S (797 mm) (826 mm) Refer to Position and Level the Tumbler to temporarily reduce the heights of these models. Models 63.45 in.
  • Page 7: 170 Pound Tumbler Dimensions And Exhaust Outlet Locations

    170 Pound Tumbler Dimensions and Exhaust Outlet Locations Models 33.86 in. 32.5 in. 170L/N/S (860 mm) (826 mm) Refer to Position and Level the Tumbler to temporarily reduce the heights of these models. Models 42.38 in. 170L/N/S (1076 mm) © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT 3-09-71 TOP VIEW OF EXHAUST...
  • Page 8: Electric And Gas Connection Locations For Gas Models

    Tumblers – 120 and 170 Electric and Gas Connection Locations for Gas Models 120L/N Models 120L/N 170L/N NOTE: These figures are approximate dimensions only. © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT Electrical Connection 18.34 in. 77.84 in.
  • Page 9: Electric And Steam Connection Locations For Steam Models

    Electric and Steam Connection Locations for Steam Models 120S Models Diameter 3/4 in. NPT 120S 3/4 in. NPT 170S Models Diameter 3/4 in. NPT 120S 1 in. NPT 170S Models 120S 170S © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT 3-09-71 Steam Inlet 35.875 in.
  • Page 10: Electric Connection Location For Electric Models

    Tumblers – 120 and 170 Electric Connection Location for Electric Models TMB2336N Models 35.81 in. 85.64 in. 120E (910 mm) (2175 mm) © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT 3-09-71...
  • Page 11: Installation

    Tumblers – 120 and 170 Installation Pre-Installation Inspection Upon delivery, visually inspect the crate, carton and parts for any visible shipping damage. If the crate, carton, or cover is damaged or signs of possible damage are evident, have the carrier note the condition on the shipping papers before the shipping receipt is signed, or advise the carrier of the condition as soon as it is discovered.
  • Page 12: Tumbler Enclosure

    Tumblers – 120 and 170 Tumbler Enclosure To reduce the risk of severe injury, clearance of tumble dryer cabinet from combustible construction must conform to the minimum clearances. NOTE: Shaded areas indicate adjacent structure. 0.5 in. (13 mm) recommended between machines for removal or installation. Allow 2-4 in.
  • Page 13: Exhaust Requirements

    Exhaust Requirements WARNING A drying tumble dryer produces combustible lint. To reduce the risk of fire, the tumble dryer must be exhausted to the outdoors. To reduce the risk of fire and accumulation of combustible gases, DO NOT exhaust tumble dryer air into a window well, gas vent, chimney or enclosed, unventilated area such as an attic wall, ceiling, crawl space under a building, or concealed...
  • Page 14: Individual Venting

    Tumblers – 120 and 170 NOTE: Exhaust ducts must be constructed of sheet metal or other noncombustible material. Such ducts must be equivalent in strength and corrosion resistance to ducts made of galvanized sheet steel not less than 0.0195 inches (0.495 mm) thick. Local codes may require additional thickness.
  • Page 15 TMB2361N TMB2361N Removable strip of panel in framing wall to permit removal of tumbler from framing wall Partition or bulkhead Minimum distance between exhaust opening and roof, ground or other obstruction: 36 in. (914 mm) 2 in. (51 mm) minimum clearance on both sides of duct Exhaust airflow –...
  • Page 16: Manifold Venting

    Tumblers – 120 and 170 Manifold Venting While it is preferable to exhaust tumblers individually to the outdoors, a main collector duct may be used if it is sized according to Figure 4 and Figure 5. This illustration indicates minimum diameters, which should be increased if the collector length exceeds 14 feet (4.3 meters) and two 90°...
  • Page 17 NOTE: Where the exhaust duct pierces a combustible wall or ceiling, the opening MUST be sized per local codes. Duct Station © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT 3-09-71 ONE MANIFOLD ASSEMBLY Figure 4 120 Pound 10 in.
  • Page 18 Tumblers – 120 and 170 CONTINUE TO A NOTE: Where the exhaust duct pierces a combustible wall or ceiling, the opening MUST be sized per local codes. Duct Station © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT TWO MANIFOLD ASSEMBLIES Figure 5 120 Pound...
  • Page 19: Electrical Requirements

    Electrical Requirements Refer to Table 5. NOTE: Minimum wire sizes are obtained from Canadian Electrical Code and are intended for use as a guideline only. Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.