Installation And Connection; Precautions And Notes On Installation And Connection - Omron POWLI BU60RE Instruction Manual

Uninterruptible power supply
Table of Contents

Advertisement

2
2

Installation and connection

2-1

Precautions and notes on installation and connection

Carry the unit considering its weight and balance, and place it on a stable
and robust base.
Dropping or toppling the unit may cause injury.
The approximate weights of the units are 15.5 kg (BU60RE) and 18.5 kg (BU100RE).
If you drop the unit, stop using it and have it inspected and repaired.
For repair, contact us; ____
Do not hold the side of the front panel when lifting.
Injury may result if the panel comes off and falls.
Keep plastic package bags out of reach of children.
Children may suffocate if they place their heads into plastic bags.
Make sure to connect the unit's AC input plug to a commercial power
source with rated input voltage (100 VAC) and 50/60Hz frequency.
Connecting to a commercial power source with a different rated input voltage or frequency may
result in a fi re.
The unit may fail.
When an abnormality (unusual sound or smell) occurs, turn OFF the
unit's power switch to stop the output, and stop the supply of commercial
power. Disconnect the AC input plug from the wall outlet.
The socket-outlet shall be installed near the equipment and shall be
easily accessible.
When performing maintenance on the connected devices, follow the above instructions to
ensure safety.
Do not connect devices such as dryers, some solenoid valves, etc. ,
which have a half-wave rectifi er that allows only half-cycle AC power to
fl ow through.
Overcurrent may damage the UPS.
Connect the unit to a wall outlet (commercial power) with the appropriate
capacity (7.5 A or greater for BU60RE and 12 A or greater for BU100RE).
Otherwise, the power cord may be heated.
When equipment with the maximum output capacity is connected, a maximum current of 7.5 A
(BU60RE) or 12 A (BU100RE) fl ows.
Provide secure grounding.
After checking the plug shape of the wall outlet, directly connect the AC input plug of the unit
to it. A failure or leak that occurs when the unit is not properly grounded may result in electric
shock.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fi re.
Do not install the unit in other than specifi ed orientations.
Dropping or toppling the unit may cause injury.
If you install the unit in an orientation other than specifi ed, the unit cannot be protected from a
battery fl uid leakage.
Caution
(for installation and connection)
2
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powli bu100re

Table of Contents