4.4 Alcove Installation

The Jøtul F 50 TL can be installed in an alcove as
diagrammed in figs. 13.-14.
1. The stove must be installed only with double-wall chim-
ney connector.
2. Wall and ceiling protection, if used, must extend over the
entire area.
3. Alcove floor protection must consist of a UL/ULC or WHI
listed hearth pad or a non combustible material.
4. Minimum Alcove Ceiling Height:
Unprotected Surface - 72" (183 cm)
Protected Surface - 59" (150 cm)
4.5 Clearances to Fireplace Mantels
and Surrounding Trim
See the Clearance Chart on page 13 for approved clearances
to combustible materials that may be part of fireplace
construction.
Mantel and Trim clearances may be reduced by 50% with
use of shielding constructed in accordance with NFPA 211
specifications.
12
19”
(483 mm)
Maximum
48”
(1219 mm)
16”
(406 mm)
6”
(152 mm)
39 1/2”
(1003 mm)
Figure 14. Alcove with Wall Protection.
A
C
B
A: Unit to Mantel (12 in. deep)- 35 in. / 89 cm
B: Floor to Mantel-
C: Stove to 1 in. Top Trim -
D: Stove to 1 in. Side Trim -
Figure 15. Hearthmount Clearances.
8” (203 mm)
Maximum
48”
(1219 mm)
6”
(152 mm)
C
D
66 in. / 168 cm
31 in. / 79 cm
14 in. / 36 cm