Floor Protection; Using Shields To Reduce Clearances; Alcove Installation; Mobilehome Installation - Jøtul F600 Firelight Installation And Operating Instructions Manual

Non-catalytic wood stove
Table of Contents

Advertisement

4.3 Using Shields to Reduce Clearances

In all cases, clearance reduction dimensions extend from the
heat source surface to the protected combustible surface.
Pipe shields: When using listed pipe shields to reduce the
connector clearance to combustibles, it must start 1" above the
lowest exposed point of the connect pipe and extend vertically
a minimum of 25" above the top surface of the stove.
Double wall pipe: Listed double wall pipe is an acceptable
alternative to connector pipe heatshields.
Wall-Mounted Protection: When reducing clearances through
the use of wall mounted protection:
In the U.S. refer to NFPA 211, Standard for Chimneys, Fireplaces,
Vents and Solid Fuel Burning Appliances, for acceptable materials,
proper sizing and construction guidelines.
In Canada, refer to CAN/CSA-B365, Installation Code for Solid-Fuel
Burning Appliances and Equipment, also for acceptable materials,
proper sizing and construction guidelines.
Stove Mounted Heatshield: A stove rear heatshield has been
specifically designed for the Jøtul F 600.
Rear heatshield part # 154329.
No other heat shield may be used.
See pages 16-17 for complete clearance requirements and
diagrams.
Notice
Accessories for wood stoves for clearance reduction have been
developed by many manufacturers. Be sure that any accessory
you choose has been tested by an independent laboratory and
carries the laboratory's testing mark. Make sure to follow all of
the manufacturer's instructions.
Always contact your local building inspector or fire officials about
restrictions and requirements in your area. Local officials have final
authority over installation approval.

4.4 Alcove Installation

The Jøtul F 600 can be installed in an alcove situation provided:
See figures 9 and 10, page 14.
1. The stove must be installed with listed double walled pipe.
2. In a protected alcove installation both side walls and rear wall
must be protected per NFPA 211 or CAN/CSA-B365. The wall
protection must be elevated 1" from the floor and at least 1"
off the combustible wall to allow for an air-flow.
3. The height of the wall protection including the bottom air
space must be 48".
4. The bottom heatshield is required in all Alcove installations.
See page 15 for installation instructions.
5. The hearth must be constructed of noncombustible material
having a minimum R-value of 0.5 or a Type II hearth pad having
an R-value of 0.5 or greater. (see Appendix A, page 19).
6. Minimum ceiling height in an unprotected installation, off the
top of the stove is 48"(1220mm). The minimum ceiling height
off the top of the stove in a protected ceiling installation is
15"(380mm).
Use of the right side load door is prohibited in alcove installations.
Install Side Door Lock kit 155850 available from your Jøtul dealer.
4.5 Mobile Home Installations
The Jøtul F 600 has been approved for use in mobile homes in
the U.S. and Canada, provided:
1. The stove is secured to the floor or the mobile home. Floor
mounting kit #750304. The structural integrity of the mobile
home must be maintained.
2. All chimney components, including chimney sections, supports,
spark arrestor, etc., shall comply with the Standard for Factory-
built Chimneys for Residential Type and Building Heating
Appliances, UL 103 and/or CAN/ULC-S629 Standard for 650°C
Factory-built Chimneys.
3. The chimney shall be attached directly to the stove and extend
at least 3 ft. (0.9m) above the roof. Termination must be at
least 2 ft. (0.6m) above the hightest elevation of any part of
the mobile home within 10 ft. (3m).
4. In order to allow for transportation of the mobile home, the
chimney termination shall be readily removed at or below an
elevation of 13.5 ft. (4.1 m) above ground level and reinstalled
without use of special tools or instructions.
5. A spark arrester must be installed at the termination. The net
free area of the arrester above the chimney outlet must not
be less than four times the net area of the chimney outlet,
and the vertical height of the arrester must not be less than
one-half the diameter of the chimney flue. Openings shall
not permit the passage of a sphere having a diameter larger
than 1/2" (12.7 mm), and shall permit the passage of a sphere
having a diameter of 3/8" (9.6 mm).
6. Direct connection of the stove to an outside air source is
required. Use Outside Air Kit 154333. Do not substitute any
other connection method or device. See page 11 for more
details. Duct termination must not be installed at a level that
is higher than the air inlet located at the bottom of the stove.
7. When the chimney exits the mobile home at a location other
than through the roof, and exits at a point 7 ft. (2.1 m) or
less above the ground level, a guard or other method of
enclosing the chimney, must be provided at the point of
exit for a height up to 7 ft. Openings of this chimney guard
shall not permit penetration of a 3/4 in. (19.1 mm) diameter
rod, or contact with the chimney by a 1/2 inch (12.7 mm)
diameter rod inserted through the opening a distance of
4 inches (102 mm).
DO NOT INSTALL THE STOVE IN A BEDROOM OR SLEEPING AREA.
Always consult your local building inspector or fire officials about
restrictions and requirements in your area prior to installing the
stove.
139682-R04 F 600 9/19