Alcove Installation; Mobile Home Installation - Jøtul Oslo Installation And Operating Instructions Manual

Catalytic wood heater
Table of Contents

Advertisement

139946-18 F 500 V3 Oslo May 2022
NOTE:
Accessories approved for clearance reduction
have been developed by many manufacturers. Be sure that
any accessory you choose has been tested and listed by an
independent laboratory and carries the laboratory's testing
mark. Follow all of the manufacturer's instructions.
Always contact your local building inspector or fire officials about
restriction and requirements in your area. Your local officials
have final authority for installation approval.

4.4 Alcove Installation

Use of the left side load door is prohibited in alcove
installations. Install 155840 Side Door Lock kit available from
your dealer.
Ths appliance may be installed in an alcove provided: (See
figures 9 and 10, page 17.)
1. The stove must be installed with listed, double-wallpipe.
2. In a protected alcove installation both side walls and rear
wall must be protected per NFPA 211. The wall protection
must be elevated 1"(24,5mm) from the floor and at least 1"
(24,5mm)off the combustible wall to allow for cooling air-
flow.
3. The height of the wall protection including the bottom air
space must be 48"(1219mm).
4. Clearance specifications are designated between the stove
plates and the combustible wall surface.
5. The bottom heatshield is required in all Alcove
installations. See figure 16, page 19 for installation
instructions.
6. Hearth protection material must consist of:
a) a UL/ULC listed Type II Thermal Floor Protector or,
b) material having a minimum r value of 1.6 (see appendix
B).
7. Minimum ceiling height in an unprotected installation,
off the top of the stove is 41"(1041 mm). The minimum
ceiling height off the top of the stove in a protected ceiling
installation is 15"(380mm).
Use of the left side load door is prohibited in alcove
installations. Install 155850 Side Door Lock kit available from
your dealer.
8
4.5 Mobile Home Installations
The F 5
V3 has been approved for use in mobile homes in
00
the U.S. and Canada provided:
1. The stove is physically secured to the floor or the mobile
home. Use Jotul Floor Mounting Kit #750304. The
structural integrity of the mobile home must be maintained.
2. All chimney components, including chimney sections,
supports, spark arrestor, etc., shall comply with the
Standard for Factory-built Chimneys for Residential Type
and Building Heating Appliances, UL 103 Standard for
650°C Factory-built Chimneys.
3. The chimney shall be attached directly to the stove and
extend at least 3 ft. (0.9m) above the roof. Termination
must be at least 2 ft. (0.6m) above the hightest elevation of
any part of the mobile home within 10 ft. (3m).
4. In order to allow for transportation of the mobile home,
the chimney termination shall be readily removed at or
below an elevation of 13.5 ft. (4.1 m) above ground level and
reinstalled without use of special tools or instructions.
5. A spark arrester must be installed at the termination. The
net free area of the arrester above the chimney outlet must
not be less than four times the net area of the chimney
outlet, and the vertical height of the arrester must not
be less than one-half the diameter of the chimney flue.
Openings shall not permit the passage of a sphere having a
diameter larger than 1/2" (12.7 mm), and shall permit the
passage of a sphere having a diameter of 3/8" (9.6 mm).
6. Direct connection of the stove to an outside air source is
required. Use Outside Air Kit #154335. Do not substitute
any other connection method or device. See page 15 for
more details. Duct termination must not be installed at a
level that is higher than the air inlet located at the bottom of
the stove.
7. When the chimney exits the mobile home at a location other
than through the roof, and exits at a point 7 ft. (2.1 m) or less
above the ground level, a guard or other method of enclosing
the chimney, must be provided at the point of exit for a
height up to 7 ft. Openings of this chimney guard shall not
permit penetration of a 3/4 in. (19.1 mm) diameter rod, or
contact with the chimney by a 1/2 inch (12.7 mm) diameter
rod inserted through the opening a distance of 4 inches (102
mm).
DO NOT INSTALL THE STOVE IN A BEDROOM OR
SLEEPING AREA.
Always consult your local building inspector or fire officials
to determine other mobile home restrictions and requirements
in your area prior to installing the stove.