9.7.10. High Temperature Protection
• During heating operation, when outdoor temperature is more than 35°C for 15 minutes, compressor stops in order to protect the
compressor.
• After 3 minutes (restart delay control) of waiting, if thermostat is ON, outdoor unit restart.
9.7.11. Pump-down Control
• To enable pump down operation, at outdoor PCB, set the DS1and DS2 to OFF position.
• Press Test Run button for 1 second.
• During Pump Down operation, push the Test Run button again for 1 second to stop the pump down operation.
• The pump down operation run for 10 minutes.
9.7.12. Thermostat Control
• Depending on differences between room temperature and setting temperature, compressor operation is decided and starts
operation.
• If temperature difference matches values shown below, thermostat switches off or on accordingly.
9.8.

Protection Control

9.8.1.
Outdoor Low-pressure Protection Control
• The purpose of low-pressure protection control is gas leakage detection control.
• The low-pressure protection control starts when low-pressure switch is activated less than 15 minutes after compressor startup.
During heating operation or defrost control low-pressure detection does not start.
• During this protection control, compressor is shut down, indoor unit is set to thermo-off status.
• After 6 occasions, suction pressure error is displayed; all operation stopped except outdoor fan remaining heat removal control.
Thermostat OFF
Cooling Mode
Soft Dry Mode
Heating Mode
Thermostat ON
-1.5°C
-2.5°C
3.5°C
45
-0.5°C
-2.5°C
2.5°C