NOTE 2
Do not short the remote control unit wires to each other. (The protection circuit will be activated and the units will not operate.)
Once the cause of the short is eliminated, normal operation will then be possible.
NOTE 3
When running the units in heating mode during test operation, be sure to run the units in cooling mode first before selecting this
mode. If heating mode is selected first, it may cause problems with operation of the compressor.
NOTE 4
Be sure to select cooling mode first, and run the unit in this mode for 5 minutes or more.
If the cooling operation is not executed first for five minutes or more, the heating operation can not be executed.(Test operation will
be cancelled automatically after 30 minutes.)
NOTE 5
Test operation mode should always be cancelled once test operation itself has been completed.
NOTE 6
If the self-diagnosis function reports a problem but more than one problem has developed at the indoor and/or outdoor units, the
problem display on the remote control unit may not match the LED display on the outdoor unit printed circuit board. In such cases,
check both locations and remove the causes of the problems.
10.5.12. As to making the inspection after completion of work fully understood
• At the time when the work has been completed, measure and record the characteristics of test run without fail and keep the
measuring date, etc.
• Carry out the measurement regarding room temperature outside air temperature, suction and air discharge temperatures, wind
velocity, wind volume, voltage current, presence of abnormal vibration, operating pressure, piping temperature, compressive
pressure, airtight pressure as items to be measured.
• As to the structure and appearance, check following items.
Short circuit of the blow-out air
Smooth flow of the drain
Reliable thermal insulation
Leakage of refrigerant
10.5.13. As to delivery to the customer
• Request the customer to operate this air conditioner viewing instruction manual come with indoor unit in practice and explain
how to operate.
• Deliver the instruction manual to the customer without fail.
Mistake in wiring
Reliable connection of the grand wire
Looseness in terminal screw, fastening torque
M3... 69-98N.cm {7-10kgf.cm} M4... 157-196N.cm {16-20kgf.cm}
M5... 196-245N.cm {20-25kgf.cm}
73