9.8.9.
Valve Error Detection Control
• This control is to protect the compressor.
• Valve error is detected if comply with condition below:
- Power is on for the first time and within 5 minutes from compressor starts (However, the unit is considered power on for first
time when compressor starts operating continuously for 7 minutes).
- Indoor heat exchanger temperature at compressor start -3°C < current heat exchanger temperature for 1 minutes.
• During this error, four-way valve error is displayed; compressor is shutdown.
9.8.10. High-pressure Switch Disconnection Error Detection Control
• High-pressure switch disconnection is detected when high-pressure switch input continuously open for 1 minutes while the
compressor shutdown.
• During this error, high-pressure switch error is displayed.
9.8.11. Low-pressure Switch Disconnection Error Detection Control
• Low-pressure switch disconnection is detected when low-pressure switch input continuously open for 1 minutes while
compressor shutdown.
• During this error, low-pressure switch error is displayed.
9.9.

Test Run

• Test run is necessary after installation is completed.
• To enable forced cooling test run, at outdoor PCB, set the DS1 to ON position and DS2 to OFF position.
• To enable forced heating test run, at outdoor PCB, set the DS1 to ON position and DS2 to ON position.
• Press Test Run button at outdoor pcb for 1 second.