13.3.2. Heating Performance

Model
CS-F24DB4E5
Heating capacity
7.1kW
Ambient
Temperature Air Entering Condenser (°C D.B.)
Return
-6°C
Air
HC
D.B.
kW
15
5.18
20
4.90
25
4.62
HC: Heating Capacity
Heating capacities are based on conditions
Single phase, 50Hz 230V
Indoor temp. 20°C D.B.
Outdoor temp. 7°C D.B. 6°C W.B.
Standard air volume 18 m
0°C
6°C
12°C
HC
HC
HC
kW
kW
kW
6.21
7.46
8.66
5.86
7.10
8.52
5.54
6.75
8.17
3
/min
Ambient
Temperature Air Entering Condenser (°C D.B.)
Return
-6°C
Air
IPT
D.B.
kW
15
1.65
20
1.75
25
1.84
IPT: Heating Power Consumption
122
0°C
6°C
12°C
IPT
IPT
IPT
kW
kW
kW
1.89
2.24
2.64
2.01
2.36
2.74
2.12
2.48
2.80