5.7

Alarm Menu (Only for WBL400 models)

The possible status screen for this menu are shown below. Note: Alarms produce a top level status
message only. There is no alarm relay available.
Alarm OFF
Alarm LOW ALRM
Alarm HI ALRM
Alarm % Low
Alarm % High
2000 S/cm 68° F
Alarm
EXIT
Alarm
Alarm % Low
This is the % below the blowdown set point that the LOW ALARM will activate. If the set point is
1000 and the % Low setting is 20 then the Low alarm will activate at 800.
This is the % above the blowdown set point that the HIGH ALARM will activate. If the set point is
1000 and the % Low setting is 20 then the High alarm will activate at 1200.
μ
HI ALRM
ENTER
PREV.
NEXT
Alarm
HI ALRM
Alarm % High
20
Figure 14 Alarm Menu
Alarm Menu
Possible status screens
Alarm
OFF
Alarm
LOW ALRM
HI ALRM
20
27