Alarm (A or B) Menu

The Alarm menu screen will appear as follows:
Alarm OFF
Alarm LOW ALRM
Alarm HI ALRM
Set % Low
Set % High
A: 2000 S
Alrm
HI
EXIT
ENTER
Alarm
HI ALRM
Alarm % Low
This is the % below the bleed set point that the LOW ALARM will activate. If the set point is 1000
and the % Low setting is 20 then the Low alarm will activate at 800.
This is the % above the bleed set point that the HIGH ALARM will activate. If the set point is 1000
and the % Low setting is 20 then the High alarm will activate at 1200.