Omron POWLI BX35F Instruction Manual page 47

Uninterruptible power supply (ups)
Table of Contents

Advertisement

8. Example of the use of the Contact Signal circuit
● Example of the use of the BU signal
● Example of the use of the BS signal
9. Precautions and notes on the use of the Contact Signal
● When connecting a device that generates counter electromotive force to the signal output circuit
such as a relay, connect diodes to prevent counter electromotive force at the both end of the
relay.
● When power is restored after the unit stopped automatically during a power failure, the unit
automatically restarts and supplies power. If you do not want to start the connected devices, turn
OFF their switches or set the auto restart setting (setting switch 2) to ON. (See page 32.)
BU
COM
UPS side
Connecting cable
(twisted or
shielded)
BS
UPS side
COM
Connecting
System side
cable (twisted
or shielded)
Explanation
TLP627
To port on PC
12V
System side
.
From port on PC
GND
Notes
45
6. Using the Contact Signal

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powli bx50fPowli bx50fwPowli bx75sw

Table of Contents