Uninterruptible Power Supply (UPS) BW40T/BW55T/BW100T/BW120T Instruction Manual This manual describes the significant points to be noted to maintain the safety while using the ▪ UPS. Therefore, ensure reading it carefully before installation and start using the UPS. Store this manual near the UPS so it can be referenced whenever required.
+ Carefully observe the conditions and environment for usage described in this instruction manual. + Please contact us at OMRON Electronic Equipment Customer Support Center for the use of the critical systems especially requiring the reliability.
Procedure from installation to operation Procedure from installation to operation Shows the procedure from installation to operation. BW40T/BW55T/BW100T/BW120T...
3-1-6 Pausing the beep sound ....................26 Beep sound - How to see the display ............27 UPS functions ..................31 Suspending a beep ..................31 Self-diagnostic test ..................31 UPS setting utility software ................32 Measuring the backup time ............... 33 BW40T/BW55T/BW100T/BW120T...
Page 6
8-2-2 Simple Shutdown Software ....................54 8-2-3 What is the Power Attendant Lite ..................54 8-2-4 The setting of the UPS monitoring software............... 55 References ..................57 Specifications ....................57 Dimensions ....................58 Circuit block diagram ..................59 Related products ..................60 BW40T/BW55T/BW100T/BW120T...
+ There is a risk of injury if the product falls or drops. + Unit mass: BW40T/BW55T: 4.5kg BW100T/BW120T: 7.9kg + In a case of dropping the UPS, stop using the unit and immediately ask for the inspection and repair. For information about repair, contact Omron Electronics Repair Center. BW40T/BW55T/BW100T/BW120T...
Page 8
AC power supply, such as dryer and some solenoid valves. + Overcurrent may damage the Uninterruptible Power Supply. Connect to the power outlet (commercial power supply) with the following current capacity. BW40T: 5.0A or higher BW55T: 6.0A or higher BW100T: 11.0A or higher BW120T: 12.0A or higher + Power wiring can catch heat.
Page 9
+ Electric shock or fire can occur due to the cable damage or heat generation. + Stop using the UPS if the cable has damage and immediately ask for the repair. For information about repair, contact Omron Electronics Repair Center. All the accessories packaged together are available only when using the UPS.
Page 10
Safety Precautions For information about repair, contact Omron Electronics Repair Center. Replace the battery as soon as the life ends, or discontinue the use of the UPS. + Continue using it may cause a fire or electric shock due to the liquid leakage.
Page 11
Do not use any other batteries than specified by our company. It may cause fire. + Product models: Battery pack for replace: For BW40T/BW55T: BWB55T For BW100T/BW120T: BWB120T Do not replace the battery pack in a place where combustible gas exists.
Page 12
+ That may cause electric shock, heat generation or burn injury. + Electric energy may remain even in a used battery pack. Do not throw the battery in the fire or break it. + The battery may explode or leak dilute sulfuric acid. BW40T/BW55T/BW100T/BW120T...
Page 13
However, adjust the frequency of the generator to match with the commercial power supply. Do not use the unit for the frequent backup operation. + Battery may deteriorate to the extent where the specified backup time cannot be maintained. BW40T/BW55T/BW100T/BW120T...
Page 14
+ This unit uses lead acid batteries. The lead acid batteries are precious recyclable resources. Please cooperate recycling. For more details about recycling, contact Omron Electronics Replace Center, or download the application form for the replacement service from our website, fill the required fields and send it to our Replace Service Center.
Page 15
You can enable/disable automatic restart on "Setting" screen (P.30.) EFERENCE Prepare for an unexpected circumstance, such as the data protection and system redundancy. + The Uninterruptible Power Supply (UPS) may stop the output due to the internal circuit failure. BW40T/BW55T/BW100T/BW120T...
When using the UPS as a UL standards complied product, do not use 3P - 2P conversion plug. <Customer Registration> Fill out the necessary information on the attached customer loyalty registration card and send us back within one month from the date of purchase. User registration is accepted at our homepage (http://www.omron.co.jp/ese/ups/regist/regist.html.) BW40T/BW55T/BW100T/BW120T...
Name of Each Part The followings list the names of the UPS parts. Refer to "2Installation and connection” (P.20,) "3Operation of the Uninterruptible Power Supply (UPS)” (P.25) and other sections for the details description of each function. + Front BW40T/BW55T/BW100T/BW120T...
Page 18
1 Preparation 1-3 Name of Each Part + Back BW40T/BW55T BW40T/BW55T/BW100T/BW120T...
The operation display section can be rotated by 90 degrees by the placement whether it is vertical or horizontal. Pull out the operation display section, rotate it, and press it down. *Do not rotate it 90 or higher degrees. Otherwise, the cord may be damaged. 1-3-1 Button functions BW40T/BW55T/BW100T/BW120T...
Correct Direction of Installation Watch your fingers and other parts of your body to not to be pinched between the parts. * Paste the rubber feet (for the horizontal installation) in the four corners of the bottom surface. BW40T/BW55T/BW100T/BW120T...
Connect the UPS and PC with a connection cable when using Windows standard UPS service, an automatic shutdown software for free download. "8Using the UPS monitoring software” (P.50) EFERENCE * This operation is not required when not using the automatic shutdown software. BW40T/BW55T/BW100T/BW120T...
The UPS is shopped after fully charged; however, the backup time may be shorter due to the natural discharge at the time of first use. We recommend you to start using the UPS after fully charging it. BW40T/BW55T/BW100T/BW120T...
Page 23
12 hours, and then return to the procedure 4 again. - If the problem persists after attempting the above two methods, contact OMRON Electronic Equipment Customer Support Center. Connect "AC input" plug to the power outlet (commercial power supply) again.
In this case, the backup immediately starts the moment the power failure occurs just after start charging. "2-4Charging the Battery” (P. 24) EFERENCE All the preparation for starting the operation has been completed. BW40T/BW55T/BW100T/BW120T...
- When the self-diagnosis test isn’t executed, it immediately switches to AC output from the commercial power supply. Status display Output the power (in a state where Power output outlet connected equipment is conducted) - The battery is charged automatically while running. BW40T/BW55T/BW100T/BW120T...
- Even in power OFF state, the battery is automatically charged as long as the commercial power supply is available. 3-1-6 Pausing the beep sound The activated beep sound pauses by pressing "Stop buzzer/Enter" button. You can enable/disable beep sound on "Setting" screen (P. 30.) EFERENCE BW40T/BW55T/BW100T/BW120T...
Support Center for any doubts. Charge stopped due to abnormal charging voltage of the battery (over) Ask for the repair as a problem is Charge stopped due to suspected with the UPS. abnormal charging voltage of the battery (under) BW40T/BW55T/BW100T/BW120T...
Page 28
(Alarm only; output continues) battery on your own. Interval *1 Output voltage displays. *2 Backup standard time displays. The status display can be switched among each detected value with "Select" button. The detected value transits as follows. BW40T/BW55T/BW100T/BW120T...
Page 29
The switch turns from a lighted state to blinking state (if it does not blink, repeat the step from the procedure 4.) Press the "Stop buzzer/Enter" switch and "Select" switch at the same time to return to the normal screen (the buzzer sounds). BW40T/BW55T/BW100T/BW120T...
Page 30
With period: SJ.1 - SJ.9 = Up to 54 seconds by 6 minutes. Without period: SJ1 - SJ9 = Up to 9 minutes by 1 minute. The setting utility allow to set up to 9999 minutes within 10 - 59 seconds by 1 second. BW40T/BW55T/BW100T/BW120T...
"Buzzer stop/Enter" button, self-diagnostic test start and display [FU]. As the test complete normally, [C00] stops blinking, and the self-diagnostic test is complete. Press "Buzzer stop/Enter" button and "Scroll" button simultaneously. The buzzer sounds like 'p' (continuous sound) and back to the normal screen. BW40T/BW55T/BW100T/BW120T...
(6) Startup delay time setting (7) Startup battery charge capacity setting For details, refer to the UPS utility software instruction manual. UPS setting utility software and UPS setting utility software instruction manual can be downloaded from our website (http://www.omron.co.jp/ese/ups/support/download/download.html). BW40T/BW55T/BW100T/BW120T...
For devices that use the VA or A indication, convert the capacity into W. Multiply the value indicated on devices by the value in the right table for conversion. When the power factor is unknown, enter “1”. The power factor usually ranges between 0.6 and 1. BW40T/BW55T/BW100T/BW120T...
Goes ON when an internal failure of the UPS occurs or when the battery life counter expires. Battery Replacement Signal Goes ON when the self-diagnostic test output (WB) determines that battery replacement is necessary due to deterioration or when the battery life counter goes off-scale. BW40T/BW55T/BW100T/BW120T...
(BS) . You can download the setting utility for free from our homepage. Note: Dealing with unused signal cables To prevent the malfunction, take measures such as to cut or isolate stripped wires (exposed conductive part) to prevent to contact. BW40T/BW55T/BW100T/BW120T...
Page 37
Type of Isolated output through a photo signals coupler Signal output (BU/BL/TR/WB) Voltage: 35V or less Maximum Rated current: 50mA Signal Input Voltage: 5V-15V Input of backup stop signal condition (BS) Input circuit Isolated input by a photo coupler BW40T/BW55T/BW100T/BW120T...
The nearer the end of the life is, the more rapidly deterioration proceeds. 7-1-1 Life of battery (estimated replacement timing) Ambient Life of battery temperature 25 degrees 5 years Celsius 30 degrees 3.5 years Celsius 40 degrees 1.7 years Celsius BW40T/BW55T/BW100T/BW120T...
UPS, and disconnect the AC input plug from the wall. If an input power supply error such as a power failure occurs when replacing the battery while in operation, backup cannot be performed and output stops Do not replace the battery during backup operation. Output will stop. BW40T/BW55T/BW100T/BW120T...
Page 40
The lead-acid batteries are precious recyclable resources. Please cooperate recycling. For information on recycling, please contact the replacement service center of OMRON, otherwise after downloading and filling out the replace service application from our homepage, send it to our replacement service center.
7 Maintenance and Inspection 7-2 Replacing the battery 7-2-1 How to replace a battery - BW40T/BW55T * Work carefully not to slide and fall the unit. Lay it slowly so that the left side of the unit is upward. both hands put on the battery cover and slide it above to remove while putting the nail plate on the lower of the cover.
Page 42
Then, grabbing the battery cable (black), pull it out from the battery connector. Remove the battery having the label. Remove the battery with both hands while being careful not to drop it. BW40T/BW55T/BW100T/BW120T...
Page 43
Then, insert the connector of the battery cable (black) to the negative terminal. ●Replacement battery pack For BW40T / BW55T: Model BWB55T Fit the groove of the battery cover to the unit and slide it to attach it. Reset the battery life counter.
Page 44
<When replacing it while [the AC input] plug is not connected to a wall outlet> Connect [the AC input] plug to a wall outlet and do the above operation No. 1,3,4,5. Write the battery replacement date on the included battery replacement date label, and attach the label on the visible place. BW40T/BW55T/BW100T/BW120T...
Page 45
Lay it slowly so that the left side of the unit is upward. Pull the front cover towards you to remove it by hooking a finger. *Don’t twist the cable and put the cable between the battery while taking the front cover off. Doing so will cause disconnection. BW40T/BW55T/BW100T/BW120T...
Page 46
Slide it by holding the protruding portion of the plate cover to the right (1) and pull it towards you (2) to remove it. *If lay the front cover aside, detach the cable from the catch. Remove the battery pack by pulling the tapes in its both sides. BW40T/BW55T/BW100T/BW120T...
Page 47
You may hear a “pop” sound when you connect the battery, but this sound is not abnormal. Attach the metal cover to the unit (1) and slide it the left (2) to fix it. *If you detach the cable from the catch, put the cable in the catch. BW40T/BW55T/BW100T/BW120T...
Page 48
<When replacing it while [the AC input] plug is not connected to a wall outlet> Connect [the AC input] plug to a wall outlet and do the above operation No. 1,3,4,5. Write the battery replacement date on the included battery replacement date label, and attach the label on the visible place. BW40T/BW55T/BW100T/BW120T...
Stop all the connected devices and the UPS and disconnect the AC input plug from a wall outlet (commercial power). Then, remove dust with a dry cloth and connect again. Connecting the equipment “2-2How to connect the equipment” Page21 EE ALSO BW40T/BW55T/BW100T/BW120T...
When an input power supply abnormality (power failure, etc.) occurs, UPS monitoring software can be used for shutting down connected computers. According to usage, download and use necessary software from our home page: (http://www.omron.co.jp/ese/ups/support/download/download.html). Refer to the following table for the response situation for OS. Notes...
PowerPC version is not supported When using macOS 10.12/Mac OS X 10.11 and Mac OS X Server v10.11 in Ver.4.7, it is necessary to set OS. For details, refer to our homepage. Cent OS Ver.6.x、Red Hat Linux Ver.5.x、Asianux Server 3 is not supported. BW40T/BW55T/BW100T/BW120T...
● Linked shutdown ● ● Redundant power supply ● support Remote UPS management ● ● Mail send ● Telnet connection ● ● SYSLOG support ● * This function is available only for windows. Mac and Linux are NOT available. BW40T/BW55T/BW100T/BW120T...
Page 53
When a problem such as a power failure occurs, a notification email describing the problem can be sent to the system administrator. Telnet connection Settings such as shutdown parameters can be made via the Telnet connection. SYSLOG support UPS management information can be recorded in SYSLOG. BW40T/BW55T/BW100T/BW120T...
Also, you can perform the desired operation by setting the automatic start/stop of the battery mode operation based on the scheduled setting. For details, see the manual for the above software. Visit our website to download the manual for this software: http://www.omron.co.jp/ese/ups/support/download/download.html BW40T/BW55T/BW100T/BW120T...
To manually start up this unit after it has been stopped by a scheduled operation, turn OFF the power button and turn it back ON again. To stop the unit when it is in operation, turn OFF the power switch. BW40T/BW55T/BW100T/BW120T...
Page 56
If, after a power failure occurs, the power is restored while auto shutdown processing is being performed, UPS output stops once after the set time elapses. After shutdown processing is complete, do not turn ON the computer until the UPS has finished restarting. BW40T/BW55T/BW100T/BW120T...
9 References 9-1 Specifications 9 References Specifications Model BW40T BW55T BW100T BW120T Operation method Full-time commercial power supply method Method method Natural air cooling Connectable devices PC, display, and peripherals Rated input voltage AC100V Startup voltage range and input Standard sensitivity setting 86±3 to 114±3 VAC voltage range High voltage sensitivity setting 95±3 to 108±3 VAC...
Make sure that both the VA value and the W value of the load capacity connected to the UPS are within the range specified here. At ambient temperature of 25 degrees Celsius and with battery in initial state. The height does not include the height of rubber feet. Dimensions Unit: mm <BW40T/BW55T> BW40T/BW55T/BW100T/BW120T...
9 References 9-4 Related products Related products For BW40T/BW55T For BW100T/BW120T Replacement battery pack BWB55T BWB120T Bracket BWP55T BWP120T USB cable BUC30 Contact signal cable BUC31 BW40T/BW55T/BW100T/BW120T...