Omron POWLI BX35F Instruction Manual page 35

Uninterruptible power supply (ups)
Table of Contents

Advertisement

● Power output stop delay time setting (setting switches 5 and 6 ) ... Factory-
shipped setting: OFF and OFF (Only for BX50FW and BX75SW)
The UPS delays the shutdown timing.
If the user sets "switch 5: ON, switch 6: ON", the UPS does not stop the output, even if the backup stop (BS) is
valid.
<Note>
The remote ON/OFF signal is not related to this setting.
When the remote ON/OFF signal is "High", the UPS stops the output immediately.
ON
1
Setting switch 5 Setting switch 6
OFF
ON
OFF
ON
AC input
ON
OFF
BS signal
ON
OFF
UPS output
ON
OFF
This timing is 10 ms or 10 sec.
Timing corresponds to the settings
for switch 7 .
2
3
4
5
6
7
8
Power output stop
delay time
OFF
0 second
OFF
60 seconds
ON
120 seconds
Does not stop
ON
power output
Shutdown delay timing
This delay corresponds to the settings
for switch 5 and switch 6 .
33
4. Operation