Interpreting Beeps And Displays - Omron POWLI BX35F Instruction Manual

Uninterruptible power supply (ups)
Table of Contents

Advertisement

4-3 Interpreting beeps and displays

1. Displays and beeps during normal operation
Status
Battery
No.
indicator
replacement
1
2
3
2. Displays and beeps while testing
4
5
3. Displays and beeps during power failure or AC input error
6
7
8
9
10
4. Displays and beeps when there is an equipment failure
11
12
Beep
Output Charging
None
OFF
OFF
None
OFF
ON
None
ON
ON
OFF
None
ON
Discharging
OFF
None
ON
Discharging
Intermittent
OFF
4-second
ON
Discharging
intervals
Intermittent
OFF
1-second
ON
Discharging
intervals
OFF
None
OFF
Discharging
None
OFF
(ON)
None
OFF
(ON)
Intermittent
ON, or
0.5-second
ON
Discharging
intervals
ON, or
Continuous
OFF
Discharging
Description
No AC input
Operation stopped
There is AC input
Power switch "OFF"
Power switch "ON"
Operating normally
Self-diagnostic test in progress
Auto battery test in progress
Backup is operating due to power failure or
AC input error. The battery will be depleted
if backup operation continues.
(Same as above.)
Battery level is low, so output will stop soon.
Battery is dead, so output stopped.
(This is displayed only for a few seconds.)
AC input voltage or frequency is
too high (over)
Power switch "OFF"
AC input voltage or frequency is
too low (under)
Power switch "OFF"
There are too many connected devices and
the rated capacity is exceeded. If this
status continues for 5 minutes or more, the
status No. 12 occurs and output stops.
Stopped due to excess connection
capacity. When the connection capacity is
120% or more, the unit immediately enters
this status without first entering status No. 11.
29
4. Operation
indicates blinking
Solution
Perform shutdown
operations for the
connected devices
and stop them.
(Same as above.)
Charge the battery.
Use within the input
voltage/frequency
range described in
the specifications.
(Same as above.)
Reduce the number
of connected
devices until the
display appears as
in status No. 3.
Turn OFF this unit
and all connected
devices. Reduce the
number of connected
devices, and then turn
ON this unit and the
connected devices.