• Reduce the Max Master number down to the
minimum needed for that network—see
vanced) Communications (BACnet) on page
• Install latest driver and check latency settings.
See Latency Settings for KMD-5576 Service Bul-
letin (SB0308A) on the KMC web site.
• See also

MS/TP Network Communication Issues

below.
MS/TP Network Communication Issues
NOTE: In firmware R2.0.0.6 and later, Configure
must first be selected before any values
can be changed.
• Check the phasing of the power and network
lines. See
Wiring Issues on page
• Check route status, MAC address, and device in-
stance numbers (especially for duplicate numbers
on the network)—see
tions (BACnet) on page 14
Device Properties on page
• Check that EOL switches are fully latched in the
correct positions (see the relevant FlexStat Instal-
lation Guide).
• Check baud rate—see
tions (BACnet) on page
• Reduce the Max Master number down to the
minimum needed for that network—see
vanced) Communications (BACnet) on page
• Ensure wiring is correct. See
page
39.
• If a new BAC-12xxxx FlexStat is installed on an
old BAC-10000 series backplate, the input/power/
communications terminals are misaligned. MS/
TP communications may be damaged. Replace
the old backplate with the new backplate that is
designed for and included with the BAC-12xxxx.
If the FlexStat is damaged, replace it with another
BAC-12xxxx.
CAUTION
The 6-external-input BAC-12xxxx/13xxxx/14xxxx
series are NOT COMPATIBLE WITH THE
BACKPLATES OF OLDER (3-external-input) BAC-
10000 Series FlexStats! If replacing an older
3-external-input FlexStat, replace the backplate as
well.
FlexStat
(Ad-
14.
39.
(Advanced) Communica-
and
(Advanced) BACnet
17.
(Advanced) Communica-
14.
(Ad-
14.
Wiring Issues on

Cover, Display, and Reset Issues

Cover Binds on Backplate

• To remove the cover, turn the hex screws in the
bottom and top of the FlexStat CLOCKWISE
only until they clear the cover. Pull the cover
away from the backplate (mounting base).
CAUTION
To prevent mounting screws from causing damage
to the case or circuit board, DO NOT TURN THE
SCREWS IN FARTHER THAN NECESSARY to remove
the cover. Using a power screwdriver on these
screws is not recommended. Also, use only the
mounting screws supplied by KMC Controls since
other types of screws may damage the FlexStat.
• Carefully remove the FlexStat cover from the
backplate and inspect for bent pins and/or termi-
nal socket connectors. If cover pins are bent, use
a needle-nose pliers to straighten them. If socket
connectors are bent, use a pointed object (such
as a thumbtack or straightened paperclip) to
straighten them. (Pushing the pointed object into
the socket from the back side can be helpful.)
• Replace the backplate.
NOTE: When installing the cover on the
backplate, be sure to not pinch or dislodge
any wiring. Do not use excessive force.
If there is any binding, pull out cover
and examine pins and terminal socket
connectors.
CAUTION
The 6-external-input BAC-12xxxx/13xxxx/14xxxx
series are NOT COMPATIBLE WITH THE
BACKPLATES OF OLDER (3-external-input) BAC-
10000 Series FlexStats! If replacing an older
3-external-input FlexStat, replace the backplate as
well.