Electrical connections 230 V a.c.
Terminal Description
1
L
Voltage supply 230 V a.c.
2
N
Voltage supply 230 V a.c.
3
M1
Gear motor - open
Gear motor - close
4
M1
alt.: ABV thermo actuator
5
230 V a.c. supply for M1
Circulation pump for
9
P1
heating circuit
10
230 V a.c. supply for P1
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 2 to common N-terminal
Electrical connections: Max. 2 x 1.5 mm2 cables can be inserted
in each screw terminal (max. cable length: 50 m).
Important: Wrong connections cause damaged TRIAC outlets.
26
Electrical connections 230 V a.c.
Terminal Description
1
L
Voltage supply 230 V a.c.
2
N
Voltage supply 230 V a.c.
3
M1
Gear motor - open
Gear motor - close
4
M1
alt.: ABV thermo actuator
5
230 V a.c. supply for M1
Circulation pump for
9
P1
heating circuit
10
230 V a.c. supply for P1
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 2 to common N-terminal
Electrical connections: Max. 2 x 1.5 mm2 cables can be inserted
in each screw terminal (max. cable length: 50 m).
Important: Wrong connections cause damaged TRIAC outlets.
26
Max. load
0.2 VA 230 V a.c.
0.2 VA 230 V a.c.
4(2)A 230 V a.c.
Max. load
0.2 VA 230 V a.c.
0.2 VA 230 V a.c.
4(2)A 230 V a.c.
Electrical connections 24 V a.c.
Terminal Description
1
L
Voltage supply 24 V a.c.
2
N
Voltage supply 24 V a.c.
3
M1
Gear motor - open
Gear motor - close
4
M1
alt.: ABV thermo actuator
5
24 V a.c. supply for M1
Relay for circulation
9
K1
pump
10
24 V a.c. supply for K1
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 2 to common N-terminal
Electrical connections: Max. 2 x 1.5 mm2 cables can be inserted
in each screw terminal (max. cable length: 50 m).
Important: Wrong connections cause damaged TRIAC outlets.
Electrical connections 24 V a.c.
Terminal Description
1
L
Voltage supply 24 V a.c.
2
N
Voltage supply 24 V a.c.
3
M1
Gear motor - open
Gear motor - close
4
M1
alt.: ABV thermo actuator
5
24 V a.c. supply for M1
Relay for circulation
9
K1
pump
10
24 V a.c. supply for K1
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 2 to common N-terminal
Electrical connections: Max. 2 x 1.5 mm2 cables can be inserted
in each screw terminal (max. cable length: 50 m).
Important: Wrong connections cause damaged TRIAC outlets.
Max. load
1A 24 V a.c.
1A 24 V a.c.
4(2) A 24 V a.c.
27
Max. load
1A 24 V a.c.
1A 24 V a.c.
4(2) A 24 V a.c.
27