Switch 3: Maximum fl ow temperature limit
Switch 3
Max. fl ow temperature
OFF
ON
Set a maximum fl ow temperature to protect your heating
sys tem from getting overheated.
Switch 4: Running time of the motorized valve
Switch 4
Running time
OFF
ON
The running time of the motorized valve is the time it takes
the valve to move from closed to fully open position.
Select the running time of the motorized valve that suits you
best. The running time is defi ned as:
Valve stroke (mm) X actuator speed (sec./mm) = running
time.
If the thermo actuator is selected for switch 5, the setting of
switch 4 will be disabled.
16
Switch 3: Maximum fl ow temperature limit
Switch 3
Max. fl ow temperature
OFF
ON
Set a maximum fl ow temperature to protect your heating
sys tem from getting overheated.
Switch 4: Running time of the motorized valve
Switch 4
Running time
OFF
ON
The running time of the motorized valve is the time it takes
the valve to move from closed to fully open position.
Select the running time of the motorized valve that suits you
best. The running time is defi ned as:
Valve stroke (mm) X actuator speed (sec./mm) = running
time.
If the thermo actuator is selected for switch 5, the setting of
switch 4 will be disabled.
16
Your setting
45 ºC
90 ºC
Your setting
20 sec.
120 sec.
Your setting
45 ºC
90 ºC
Your setting
20 sec.
120 sec.
Switch 5: Gear motor/thermo actuator
Switch 5
Actuator type
OFF
Thermo actuator
ON
Select the gear motor or thermo actuator, depending on what
is used in your heating system.
Switches 6, 7 and 8: Addressing and time unit
selection
Switch 6 Switch 7 Switch 8
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
Set the slave address of the controller, if it is a part of a
mas ter/slave system. Set the address of the ECA 60/61, if it is
connected. See also page 32.
Switch 5: Gear motor/thermo actuator
Switch 5
Actuator type
OFF
Thermo actuator
ON
Select the gear motor or thermo actuator, depending on what
is used in your heating system.
Switches 6, 7 and 8: Addressing and time unit
selection
Switch 6 Switch 7 Switch 8
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
Set the slave address of the controller, if it is a part of a
mas ter/slave system. Set the address of the ECA 60/61, if it is
connected. See also page 32.
Your setting
Gear motor
Slave
Clock
Your
address
setting
0
built-in
1
built-in
2
built-in
3
built-in
ECA 60/61
4
address A
ECA 60/61
5
address B
Your setting
Gear motor
Slave
Clock
Your
address
setting
0
built-in
1
built-in
2
built-in
3
built-in
ECA 60/61
4
address A
ECA 60/61
5
address B
17