TESTING

The T-32-TS incorporates a short-cycle timer which can be disabled during testing by
setting slide switch 3 to the ON position. Once testing is completed, the time should
be enabled by setting the switch to OFF.

TESTING FAN OPERATION

Touch
MODE
until the word
appear. After a brief moment, the internal fan relay 'G' will energize and the system fan
should operate. Touch
FAN
moment, the internal fan relay will de-energize and the system fan will shut off.

TESTING CONVENTIONAL HEATING AND COOLING OPERATION

Touch
MODE
until the word
above the space temperature and the first stage differential. After a brief moment, the
internal heating relay 'W1' will energize and the heating system should operate. The
word
Heat
will flash continuously. If the thermostat has been configured for two stage
heating, raise the setpoint above the second stage differential and the second stage
heating relay 'W2' will energize. The word
sequence to indicate second stage has been energized.
OFF
is displayed. Touch
again until the word
Automatic
Heat
appears. Touch the
Heat
will flash twice, pause and repeat the
52
FAN
until the words
Always On
appears. After a brief
UP
arrow and raise the setpoint