INSTALLER SETUP MENU
SELECTING LOW BALANCE POINT OPTION
Menu 21:LB allows you to select a low balance point setting when the thermostat is
configured for Heat Pump or Fossil Fuel. When the outdoor temperature falls below
the balance point setting, the compressor is locked out and only auxiliary electric heat
UP
or fossil fuel furnace is used for heating. The factory default is
OFF
. Touch the
or
DOWN
arrows to select an low balance point setting.
Next
Back
Adjustable from OFF, 1° to 77°F
Remote outdoor sensor must be used
42