INSTALLATION
3. See Table 3 for minimum make up air openings required
for each model.
TABLE 3 MINIMUM MAKE UP AIR OPENING REQUIREMENTS
Model
Fresh Air Opening FT2 (M2)
ICW 6
ICW 10
ICW 15
ICW 20
ICW 30
ICW 50
ICW 60
2-6
1 (.09)
1 (.09)
1.5 (.14)
4 (.37)
4 (.37)
5 (.46)
7.5 (.69)
Gas Train Assembly
Burner Plate
Assembly
Secondary Air Damper
Top Plate Assembly
Flue Plate Cover
Flue Rope Gasket
Flue Blanket
Lifting Hook(s)
Stainless Steel Ring (oil only)
Flue Outlet
Top Refractory
Water Return
Bottom Refractory
Boiler Runners
FIGURE 2 COMPONENT VIEW OF THE ICW UNIT
ICW-IOM-2012-1001
4. If positive forced ventilation is adopted, ensure that
there will be no appreciable pressure variation in the
equipment room.
5. Avoid ventilation which creates a negative pressure
in the building as it will seriously a ect combustion
and proper operation of the burner. Please note that
exhaust fans or similar equipment can create a down
draft in the chimney or starve the burner's air supply.
Either case may result in poor combustion or nuisance
failures. A properly designed make-up air system in the
equipment room will preclude these possibilities and is
required to maintain proper combustion.
Transformer
Scroll
Burner Motor
Gaskets
Control Box
High Density
Insulation
Outside Jacket
Handhole
Castable
Refractory
Insulation