Plumbing; Electrical Installation - Aquatic ESTATE AIR-WHIRLPOOL Owner's Manual & Installation Manual

Estate air-whirlpool
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS

PLUMBING

1. After securing tub in place, normal waste and overflow and valves are installed per normal plumbing procedures, in
accordance with all state and local standards.
2. Install standard 1-1/2" trap to drain and overflow. Before proceeding, make a final operational check by filling
tub with water to overflow and operate pump for 5 minutes. Check for leaks carefully both while pump is running
and has been turned off. Allow water to stand in tub for at least 30 minutes before draining. Aquatic WILL NOT BE
RESPONSIBLE FOR WATER DAMAGE OF ANY KIND IN CONNECTION WITH ONE OF OUR WHIRLPOOL BATHS.
NOTE: For Rough-in measurements please refer to unit's technical data sheet.

ELECTRICAL INSTALLATION

WARNING: ALL ELECTRICAL CONNECTIONS SHOULD BE MADE BY A LICENSED, LOCALLY CERTIFIED ELECTRICIAN,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODES AND PROCEDURES.
WARNING: When using electrical products, precautions should always be followed, including the following:
DANGER: RISK OF ELECTRIC SHOCK!
Estate air-whirlpool baths will need to be hard-wired to the outlets provided. See the following directions and Figure on
page 12.
Two junction boxes will be mounted to the frame of the whirlpool. One of the two boxes will have one outlet and will be
labeled "Blower". Remove the cover and connect a 14/2 with ground Romex wire from a 15 amp 1-pole GFCI breaker
(not supplied) in the main circuit breaker panel. Connect the black wire to the hot side of the receptacle, the white wire
to the neutral side of the receptacle and the green wire to the ground. Replace the cover and plug in the blower.
The second junction box will have one outlet with two ports. Remove the cover from the one labeled "Main", and run
Romex 14/2 with ground from a 15 amp 1-pole GFCI breaker (not supplied) located in the breaker panel. Connect the
black wire to the hot side of the receptacle, the white wire to the neutral side of the receptacle and the green wire to the
ground. For the one labeled "Heater" run Romex 14/2 with ground from a 15 amp 1-pole GFCI breaker (not supplied)
located in the breaker panel. Connect the black wire to the hot side of the receptacle, the white wire to the neutral
side of the receptacle and the green wire to the ground. Replace the cover and plug in the pump to the outlet labeled
"Main". Plug in the heater to the outlet labeled "Heater".
CAUTION: Before use of the blower, pump, and heater, test the GFCI for proper operation. The blower, pump and
heater should turn off when the GFCI "Test" button is pushed.
12
GFCIs are not supplied, however we do specify their use.
All known code authorities require GFCIs.
Estate Air-Whirlpool Owner's Manual & Installation Guide