No.
Meaning
Blocking errors
1000
Blocking system error
...
1030
1040
DC voltage too high
1050
DC connection has incorrect
polarity
1060
Blocking system error
...
1290
1300
L and N connections mixed up
1310
System error
...
1990
Non-blocking errors
2010
Amplitude limit for feed-in phase
exceeded or undershot
2020
Grid amplitude error phase-to-
...
phase voltage
2040
2080
Network fault on feed-in phase
(voltage peak)
Installation and user guide PLATINUM® Inverter 7000 R3, 9000 R3, 11000 R3, 14000 R3, 16000 R3
Measure
▪ Isolate the inverter from the mains and
DC generator
▪ Put inverter back into operation
If measures prove unsuccessful:
▪ Inform service
▪ Check module connection
▪ Set DC isolator to 0
▪ Check DC connection
▪ Isolate the inverter from the mains and
DC generator
▪ Put inverter back into operation
If measures prove unsuccessful:
▪ Inform service
▪ Check L and N connection on AC plug
▪ Isolate the inverter from the mains and
DC generator
▪ Put inverter back into operation
If measures prove unsuccessful:
▪ Inform service
▪ Arrange for voltage amplitude of feed-
in phase to be checked
▪ Ensure that all safety devices are
switched on
▪ Ensure that all three phases are
connected
If this occurs frequently:
▪ Arrange for all contacts and safety
devices to be checked, from the
service connection to the inverter
▪ Arrange for the network quality to be
checked
Errors and troubleshooting
41