Technical Data - Platinum 7000 R3 Installation And User Manual

Hide thumbs Also See for 7000 R3:
Table of Contents

Advertisement

Technical data

9
Technical data
Input variables
Max. PV power
Max. DC power (cos ϕ = 1)
MPPT voltage range
Max. input voltage
Max. MPPT input current
Number of string inputs
Number of MPP trackers
Short circuit current
Ground fault monitoring
Output variables
Nominal power (cos ϕ = 1)
Nominal current
Max. apparent power
Max. AC current
Fuse protection on the AC side
Min. start power
Mains voltage
Mains frequency
Feed-in/monitoring phases
Max. mains impedance permitted (Z
Standby consumption
Short-circuit strength
Power factor (cos ϕ)
Max. short circuit current
Switch-on current (max. duration: 5 ms)
Ground fault monitoring
Efficiency
Max. efficiency
EU efficiency rate
Type name
44
3 AC 230 V / 400 V + N (+/– 20%)
3 feed-in / monitoring phases
)
max
Installation and user guide PLATINUM® Inverter 7000 R3, 9000 R3, 11000 R3, 14000 R3, 16000 R3
7000 R3
6,700 Wp
6,150 W
350 – 720 V
900 V
2 x 10 A
1+1
1
2 x 14 A
Isolation control
7000 R3
6,000 W
3 x 8.7 A
6,700 VA
3 x 11.9 A
3 x 16 A
20 W
50 Hz (+/– 5 %)
1 W
Yes
0.7 ind ... 0.7 cap
120 A
4 A
RCD
7000 R3
98.5%
98.2%
7000 R3-MDX

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

9000 r311000 r314000 r316000 r3

Table of Contents