KMC Controls FlexStat BAC-1xx63 Series Installation Manual page 4

6 relays, 3 analog outputs bacnet programmable thermostats
Table of Contents

Advertisement

Power Connection
The FlexStat requires an external, 24 volt, AC power
source. Use a KMC Controls Class-2 transformer to
supply power. Connect the transformer's neutral
lead to the 24 VAC Common/–/C terminal and the
AC phase lead to the 24 VAC Phase/
(See Illustration 4.) Power is applied to the FlexStat
when the transformer is plugged in.
KMC Controls recommends powering only one con-
troller/thermostat from each transformer. If installing
a FlexStat in a system with other controllers/thermo-
stats powered from a single transformer, however,
phasing must be correct and the total power drawn
from the transformer must not exceed its rating.
Accessories
HMO-10000
Horizontal or 4 x 4 handy box wall
mounting plate, light almond
HMO-10000W
HMO-10000 in white
HPO-0044
Replacement cover hex screw
HTO-1103
FlexStat firmware flash upgrade
kit
KMD-5567
Network surge suppressor
KMD-5575
Network repeater/isolator
KMD-5576
EIA-485 to USB Communicator
KMD-5624
PC data port (EIA-485) cable
(FlexStat to USB Communica-
tor)—included with the KMD-
5576 (buy for third-party EIA-232
interfaces)
SP-001
Flat blade and hex end screw-
driver (with KMC logo) for cover
hex screws
XEE-6111-040
Transformer, 120-to-24 VAC, 40
VA, single-hub
XEE-6112-040
Transformer, 120-to-24 VAC, 40
VA, dual-hub
BAC-1xx63 Series (6 Relays, 3 Analog Outputs)
Configuration
To configure the FlexStat, navigate the menus and
change settings by pressing a combination of buttons.
Press the Right (Menu) button and then the:
• Enter button to select and/or exit value editing.
~
/R terminal.
• Up/Down button to move among entries (up/
• Left/Right button to move among value fields
• Left button to return to the Home screen.
Humidity and motion sensor options are dependent
on the FlexStat model. For operation, configuration,
troubleshooting, and other information, see the
FlexStat Operation Guide.
NOTE: Applications on pages 5–9 are the packaged
4
down lines).
(left/right spaces).
MAIN MENU
ABOUT
ADVANCED
ALARM
DATE/TIME
APPLICATION
SCHEDULE
CB PROGRAMS
SETPOINTS
COMMUNICATION
SYSTEM
DATE/TIME
DEVICE
INPUTS
LIMITS
Illustration 6—Configuration Screens
programs selectable from the Advanced
> Application menu in the BAC-1xx63C
(only) models. Other FlexStat models have
other applications. Humidity and motion
sensor options are dependent on the
FlexStat model.
ADVANCED
(See
menus
on the
following
pages)
Installation Guide