Chiller Capacity And Derate Chart - Advantage Engineering Maximum Instruction Manual

Portable chiller mk series
Table of Contents

Advertisement

MK Series Portable Chiller : Air-Cooled : HE INSTRUMENT
8.8

CHILLER CAPACITY AND DERATE CHART

Standard chiller rating is at 50°F. For all other temperature settings, output
tonnage is altered as follows:
TEMPERATURE
NOTES:
If operation of the chiller at less than 48°F is required, an inhibited propylene glycol solution
is required.
Consult factory for chiller operation below 20°F.
Ambient conditions affect air cooled chiller operation and capacity. Standard rating is at
95°F entering air temperature. For ambient air conditions greater than 95°F, chiller derating
will occur. For ambients of 95-105°F, select the next larger capacity chiller. For ambients
over 105°F, consult factory.
* These ranges require special options.
OUTPUT
FULL
AVAILABLE %
°F
CAPACITY
60
105%
50
100%
45
90%
40
80%
35
70%
30
60%
25
50%
20
40%
15
30%
10
22%
5
15%
0
9%
-5
5%
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
*
*
*
*
*
Fax: 317-881-1277
Page: 78