MK Series Portable Chiller : Air-Cooled : HE INSTRUMENT
6.1
WATER SYSTEM
A.
MOTOR/PUMP ASSEMBLY: the
motor/pump assembly circulates
chilled fluid to the process loop.
The pump assembly is built of total
stainless steel to maintain water
quality (figure 6.1A).
B.
FLOW SWITCH: the flow switch is
a paddle-type switch mounted in
the from process water line. The
primary function of the flow switch
is to monitor water flow. If the flow
drops 33%, the switch will stop the
refrigerant circuit. This protects the
evaporator from freezing due to
low flow (figure 6.1B).
C.
FREEZESTAT: the freezestat aids in
protecting the evaporator from
potential freezing. The freezestat is
factory adjusted to 40°F. The
freezestat must be field adjusted for
operating with setpoints below
48°F (figure 6.1C).
6.2

REFRIGERATION SYSTEM

A.
COMPRESSOR: hermetic or semi-
hermetic compressors take low
pressure/low temperature
refrigerant gas and compress the
gas into high pressure/high
temperature gas (figure 6.2A).
B.
AIR COOLED CONDENSER: the air
cooled condenser removes BTU's
from the compressed refrigerant
gas. The action causes the gas to
"condense" into a liquid state still
under high pressure. Air flow across
the condenser is achieved via a
motor driven fan assembly or
centrifugal blower (figure 6.2B).
C.
FILTER-DRIER: the filter-drier
removes contaminants and
moisture from the liquid refrigerant
(figure 6.2C).
Pump Motor Assembly
Flow switch
Mechanical freezestat
Hermetic compressor
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
Figure 6.1A
Figure 6.1B
Figure 6.1C
Semi-hermetic compressor
Figure 6.2A
Page: 60