MK Series Portable Chiller : Air-Cooled : HE INSTRUMENT
4.
c.
rAt: programs the baud rate. The baud rate is the
data transfer rate between the unit and the host
computer. 1200, 2400, 4800, 9600 units selectable.
MACHINE: illuminates when the following parameters are
selected:
NORMAL DISPLAY MODE
Unt
- temperature/flow unit selection
EXTENDED DISPLAY MODE:
AFL
- alternate flow sensor selection
int
- internal small flow sensor selected
ALT
- large flow sensor selected
ton
- chillers size in tons
CAP
- capacity display selection
Prb
- from process probe calibration
LPt
- low pressure time delay
a.
Unt: programs temperature/flow display. Select 'F'
for Fahrenheit temperature display with GPM
(gallons per minute) flow display or select 'C' for
Celsius temperature display with LPM (liters per
minute) flow display.
b.
To show the parameters in the extended display
mode, the #3 DIP switch must be toggled. Refer to
section 5.8 for more details.
c.
AFL: programs the alternate flow sensor selection. A
'YES' will set the instrument to the internal flow
sensor. A 'NO' will set the instrument to the
external flow sensor. Typically the instrument is
programmed for the correct flow sensor from the
factory.
d.
int: a 'NO' selection for the 'AFL' parameter will
activate the internal flow sensor. The 'int'
parameter will allow a calibration factor for the
small flow sensor.
e.
ALT: a 'YES' selection for the 'AFL parameter will
activate the external flow sensor. The 'ALT'
parameter will allow a calibration factor for the
larger flow sensor.
f.
ton: programs the chiller size in tons.
g.
CAP: programs the CAPACITY DISPLAY selection. A
'ton' display will activate a continuous tonnage
display. A 'PCt' display will activate a continuous
percent display. A 'ALT' display will activate a
alternating display between tons and percent with
a 8 second cycle.