DIP SWITCH ADJUSTMENT

The 5 position DIP switch is located on
the lower right side of the CPU
board (figure 5.8A).
B.
The switches are used to set
options for machine operation.
C.
The switches should only be
changed when the instrument is
turned OFF.
1
2
3
4
The cleaning fluid source should have at least 20 psi
available. If acid cleaning, follow the instructions supplied
with the acid solution carefully.
When the procedure is complete, reinstall all water lines to
original factory orientation. Restart the unit and check for
proper operation.
Note: this procedure is not normal maintenance.
Maintaining proper water quality and filtration will
minimize the need to back flush the evaporator.
CODE_PAGE - PAGE0, 0000-0FFFF
SETPOINT RANGE - 48° - 70°F
EXT_CONFIG - DO NOT SHOW EXTENDED CONFIGURATION
CYLINER CNT - 2 STAGE UNLOADING
CHILLER_TYPE - NO UNLOADING (STD)
FACTORY SET
5
OPTIONS
CHILLER_TYPE - UNLOADING ENABLED (CYL)
CYLINDER CNT - 1 STAGE UNLOADING
EXT_CONFIG - SHOW EXTENDED DISPLAY
SETPOINT RANGE - 90° - 10°F
CODE_PAGE - PAGE 1, 10000-1FFFF
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
Typical DIP switch location
Fax: 317-881-1277
Figure 5.8A