Harman Advance Pellet Stove Installation & Operating Manual page 19

Pellet burning room heater
Hide thumbs Also See for Advance Pellet Stove:
Table of Contents

Advertisement

requirements for Terminating the venting
WARNINg: Venting terminals must not be recessed
into a wall or siding.
NOTE: Only "pellet" vent pipe wall pass-throughs
and fire stops should be used when venting through
combustible materials.
NOTE: Always take into consideration the effect the
prevailing wind direction or other wind currents will
cause with flyash and/or smoke when placing the
termination.
In addition, the following must be observed:
A. The clearance above grade must be a minimum
of 18".
1
B. The clearance to a window or door that may be
opened must be a minimum of 48" to the side and 48"
below the window/door, and 12" above the window/
door.
1
with outside air installed, the clearances are 18" to
the side and below and 9" above.
C. A 12" clearance to a permanently closed window is
recommended to prevent condensation on the window.
d. The vertical clearance to a ventilated soffit located
above the terminal within a horizontal distance of 2 feet
(60 cm) from the center-line of the terminal must be a
minimum of 18".
E. The clearance to an unventilated soffit must be a
minimum of 12".
F. The clearance to an outside corner is 11" from center
of pipe.
g. The clearance to an inside corner is 12".
= Venting Terminal
venting
H. A vent must not be installed within 3 feet (90cm)
above a gas meter/regulator assembly when measured
from the horizontal center-line of the regulator.
I. The clearance to service regulator vent outlet must
be a minimum of 6 feet.
J. The clearance to a non-mechanical air supply inlet
to the building or the combustion air inlet to any other
appliance must be a minimum of 48".
K. The clearance to a mechanical air supply inlet must
be a minimum of 10 feet.
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a paved
driveway located on public property must be a minimum
of 7 feet.
M. The clearance under a veranda, porch, deck or
balcony must be a minimum of 12 inches.
Applies)
NOTE: The clearance to vegetation and other exterior
combustibles such as mulch is 36" as measured from
the center of the outlet or cap. This 36" radius continues
to grade or a minimum of 7 feet below the outlet.
Certain Canadian and or Local codes or regulations
1
may require different clearances.
A vent shall not terminate directly above a side-walk
2
or paved driveway which is located between two
single family dwellings and serves both dwellings.
Only permitted if veranda, porch, deck, or balcony is
3
fully open on a minimum of 2 sides beneath the floor.
NOTE: where passage through a wall, or partition of
combustible construction is desired, the installation
shall conform to CAN/CSA-b365. (if in Canada)
= Air Supply Inlet
19
1
1,2
= Area where termination is not permitted
1
1
1
(b Also
1,3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents