• Fan Control: 1-3 Speeds - Cycling (Auto) or Continuous (On) - Automatic Fan Speed Staging (TB180 models only) Connections for: • Fan Coil Pipe Sensor • Remote Temperature Probe • Occupancy Control • Door Switch or Setback • Condensate Overflow Daikin IM 1019...
Failure to follow these instructions will result in death TB180-001 910119111 Staged fan control or serious injury Optional Sensors/Kits In addition to the T180 thermostat, Daikin offers optional Disconnect power before installing or servicing. sensors for occupancy detection (page 14 page 15) and...
Page 5
With the base now secured, verify that the circuit board is firmly snapped into the cover and is not dislodged. Install the cover assembly to the base, pressing firmly to engage the cover locking snaps. Daikin IM 1019...
Restores the thermostat to the factory program Time Period Indicators WAKE, DAY, EVE, and SLEEP are the names given to the four time periods per day. Each time period has its own unique setpoint temperatures as shown in Table Daikin IM 1019...
When this occurs, the thermostat will disable all outputs and illuminate the wrench symbol. A service technician should be called to determine the cause of the error. Daikin IM 1019...
COPY copy a particular day’s program to another day or group of days. Puts the thermostat in manual operation for a permanent or temporary time period. Overrides HOLD your programmed settings, but does not lose them. Daikin IM 1019...
70° F (21.0° C) 78° F (25.5° C) 8:00 am 62° F (16.5° C) 85° F (29.5° C) Evening 6:00 pm 70° F (21.0° C) 78° F (25.5° C) Sleep 10:00 pm 62° F (16.5° C) 72° F (22.0° C) Daikin IM 1019...
8, but in Step 4, select “EVE”. (Annex I‚ page 16). • Program the Sleep period for SASU by repeating steps 1 through 8, but in Step 4, select “SLEEP”. Now you’re done setting up all four time periods for SASU. Daikin IM 1019...
(normally closed CO switch) or with local the service menu table (Annex II‚ page 17). sensing (normally open CO switch). When the condensate switch activates, the T180 will display the service wrench and disable all outputs. Figure 7: Remote probe installation Daikin IM 1019...
Coil > 80°F = Winter mode. • Purge Cycle is repeated until a non-ambiguous condition is sensed. Note: If at any time the demand goes away, the thermostat will abort the purge cycle. Figure 10: Staged Fan Operation Daikin IM 1019...
• After 1 hour, the purge cycle resumes at step 1. T180 to disable the HVAC system (outputs) if a door or window is left open for more than 2 minutes. A one-time ten minute override can be initiated by pressing any thermostat key pad. Daikin IM 1019...
HVAC device due to unintentional passages or short time occupancies. The sensor may also serve as a slave sensor (Figure 12, page 15). Daikin IM 1019...
In an unoccupied mode, the sensor continually monitors the room. Any occupancy detection will set the operation to occupied mode. Figure 12: Optional equipment configuration #2 Daikin IM 1019...
Start Heat Setpoint Cool Setpoint Period Time Temperature Temperature Wake Monday Evening Sleep Wake Tuesday Evening Sleep Wake Wednesday Evening Sleep Wake Thursday Evening Sleep Wake Friday Evening Sleep Wake Saturday Evening Sleep Wake Sunday Evening Sleep Daikin IM 1019...
If enable is selected, it will activate the fan output for 10 minutes. If a different Fan Output 2- Enable Fan Medium Output menu or a different fan speed is selected the output will be disabled. 3- Enable Fan High Output Daikin IM 1019...
Page 18
Daikin Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on training, or call 540-248-9646 and ask for the Training Department.