Annex Ii - Daikin MT 180 Installation And Maintenance Manual

Mt 180 programmable thermostat
Table of Contents

Advertisement

Annex II

Table 19: Service Menu Table
Menu
Feature
1
F° or C°
3
Fan Off Delay
4
Range Low
5
Range High
6
Setback Low
7
Setback High
8
Zone Temp Offset
9
Keypad Lockout
10
Fan Mode
11
Fan Speeds
12
System Mode
Controlled Off or Off
13
Override
Front Panel Setback
14
Control
Cycled Outside Air
15
Damper
Temperature Based
16
Purge Cycle
Minimum Dead Band
17
Adjustment
18
Factory Default Reset
25
Pre-Occupancy Purge
Cycles Per Hour (CPH)
30
Cooling
Cycles Per Hour (CPH)
32
Heating
35
Heat Recovery Rate
36
Cool Recovery Rate
40
Minimum Off Time
45
Intermittent Fan
46
Intermittent Fan-On Time
47
Intermittent Fan-Off Time
71
Revision
System Test
80
Main Output (Cool)
System Test
81
Main Output (Heat)
System Test
82
Fan Output
Daikin IM 1019
Range
0- Celsius
1- Fahrenheit (Default)
0-99 Seconds (0- Default)
50-90°F, 10-32°C
(50°F- Default)
50-90°F, 10-32°C
(90°F- Default)
0- OFF
82°F, 11-27°C (55°F- Default)
0- OFF
50-90°F, 11-32°C (90°F- Default)
+/- 9°F or +/- 4.5°C (0°F- Default)
0- No keypad lockout (Default)
1- Disables System/Fan/Program
2- Disables all buttons
1- ON
2- Auto
3- ON or Auto (Default)
1- High
2- Low, High
3- Low, Med, High (Default)
OFF, Auto OFF, Heat, Cool, Auto (Default)
OFF, Heat, Cool
Heat, Cool, Auto
0- Disable (Default)
1- Enable
0- Disable (Default)
1- Enable
0- Cycles (Default)
1- Continuous
0- Time Based (Default)
1- Temperature Based
3°F (Default) 3-10°F, 1.5-5°C
0- Disable (Default)
1- Enable
0 Hours (Default)
0-3 Hours
3 CPH (Default)
0-6 CPH
5 CPH (Default)
0-12 CPH
5°F/Hr (Default)
0-18°F/Hr 0-10°C/Hr
5°F/Hr (Default)
0-18°F/Hr 0-10°C/Hr
4 Minutes (Default)
1-10 Minutes
0- Disable (Default)
1- Enable
5 Minutes (Default)
1-60 Minutes
25 Minutes (Default)
0-60 Minutes
0- Disable (Default)
1- Enable
0- Disable (Default)
1- Enable
0- Disable (Default)
1- Enable Fan Low Output
2- Enable Fan Medium Output
3- Enable Fan High Output
Description / Comments
Determines temperature displays in Fahrenheit or Celsius
The amount of time (in seconds) the lowest available fan speed will run after the
thermostat outputs are disabled.
The lowest selectable temperature setpoint value.
The highest selectable temperature setpoint value.
50-
The temperature setpoint value you want the thermostat to Heat to when the
T180 is in the Setback mode.
The temperature setpoint value you want the thermostat to Cool to when the
T180 is in the Setback mode.
Zone Temperature offset adjusts the sensed Zone Temperature displayed,
allowing calibration in the field.
This function blocks access to certain features of the device. The Service Menu
is still available if the keypad lockout is enabled.
ON- Fan is always on, regardless of demand.
Auto- Fan is only on with heating or cooling demand.
ON or Auto- User can choose either selection.
Speeds which are selectable by the user.
Sets the system modes the occupant is able to select.
When enabled, the unit will control to the Setback setpoints. This function will
also override the user mode setting of OFF if the room temperature is equal to or
above the Cool Setback setpoint or equal to or below the Heat Setback setpoint.
When enabled, Setback is shown as an available system mode selection. If
Setback mode is selected, the thermostat will control to the current Setback Heat
and Setback Cool setpoints.
The Outside Air output will cycle with heat or cool demand if Cycles mode is
chosen. The Outside Air output is active anytime the thermostat is out of the OFF
mode when Continuous mode is chosen. When in Setback the Outside Air output
will turn off.
Determines if the Purge Cycle will be Temperature or Time Based.
A changeover deadband value prevents short cycling between Heating and
Cooling modes. The value is adjustable to meet various HVAC system
requirements.
Toggles between OFF and DFLT. When factory default is desired, select DFLT.
Energizes Fan Low for selected number of hours (0-3) prior to events Wake
(Occupied 1) and Day (Occupied 2)
Defines the number of cycles per hour for cooling. A selection of 0 disables
cycling.
Defines the number of cycles per hour for heating. A selection of 0 disables
cycling.
Defines the rate in which the device achieves the comfort setpoint. 0 disables
ramp recovery.
Defines the rate in which the device achieves the comfort setpoint. 0 disables
ramp recovery.
Sets the minimum off time for both heat and cool output
If enable is selected, the intermittent fan will operate during setback operation.
(Default values will be used unless menu 46 and 47 are adjusted.)
Defines the duration in which fan low will be on. Fan On will be activated after
Fan Off time has passed.
Defines the duration in which fan low will be off. Fan Off will be activated after
Fan On time has passed. A selection of 0 will result in continuous Fan.
Upon menu selection, the firmware and configuration revision will be displayed.
If enable is selected, it will activate the main output (cool output) for 10 minutes.
Fan High will automatically turn on. If a different menu is selected the output will
be disabled.
If enable is selected, it will activate the secondary output (heat output) for 10
minutes. Fan High will automatically turn on. If a different menu is selected the
output will be disabled.
If enable is selected, it will activate the fan output for 10 minutes. If a different
menu or a different fan speed is selected the output will be disabled.
Annex II
17