On the circuit board, set the voltage selection switch
5
(Figure
3) to the appropriate position prior to application
of power.
24V = 24 VAC
110-277 V = 120, 240 or 277 VAC
Note: The circuit board is shipped with the voltage
selection switch in the 110-227 V position. For 24
VAC use, the switch must be in the 24 V position
6
The circuit board is also equipped with configuration
jumpers (JP1, JP3, and JP4 in
the application, it may be necessary to reconfigure the
following jumpers:
JP1 Jumper Selection – Remote Temperature Sensor
Local Sensing – Install JP1
Remote Sensing – Remove JP1 – Accessory sensors are
available in standard 60" lengths but can be extended to
meet application requirements.
JP3 Jumper Selection – HVAC Setback Systems
The JP3 jumper allows the T180 to be configured for
Setback, Occupancy Detection or Door Switch Only
Occupancy Operations. For further descriptions of these
conditions please see the
Notes‚ page
12.
• Setback Operation - Remove JP3
• Occupancy Detection - Install JP3
• Door Switch Only - Install JP3
JP4 Jumper Selection – 2 or 4 Pipe Operation
Connection of a pipe sensor will change the operation of
the outputs as shown in
further information on
• 2-Pipe Operation - Install JP4 - The thermostat will per-
manently disable the Secondary Output and disables sys-
tem and fan invalid modes.
• 4-Pipe Operation - Remove JP4 - Both the Main Output
(COOL) and Secondary Output (HEAT) will be avail-
able.
7
Connect the color coded thermostat wires
the line voltage wires located in the mud ring/connection
box and secure the connections with wire nuts.
Install the thermostat base to the mud ring/outlet box
8
using two furnished mounting screws. Tighten the
screws evenly but do not over tighten.
Note: An output ratings chart
inside of the base.
With the base now secured, verify that the circuit board
9
is firmly snapped into the cover and is not dislodged.
Install the cover assembly to the base, pressing firmly to
10
engage the cover locking snaps.
Daikin IM 1019
Figure
3). Depending on
Technical and Application
Table
4. (See Technical Notes for
Pipe Sensor Operation‚ page
(Figure
(Table
5) is located on the
Figure 4: Wiring Diagram
Table 4: Jumper Activation
Pipe
JP4
Sensor
Section
Water
Temp
Cold
2-Pipe
JP4-ON
2-Pipe
Cold
JP4-OFF
Note:
*Fan will not cycle on for disabled modes.
Table 5: Output Ratings
12)
Voltage
FLA
24 VAC
NA
120 VAC
5.8
240 VAC
2.9
277 VAC
2.4
Combined Load Current Not to Exceed 20 Amps
4) to
Installation Instructions
Main
Aqua
Output
Stat
(Blue Wire)
Cooling
Open
Only
Hot
Closed
Heating Only
Open
Cooling
Hot
Closed
Heating Only
Output Ratings
RES
LRA
AMPS
NA
NA
34.8
6.0
17.4
5.0
14.4
4.2
Secondary
Output
(Red wire)
Disabled
Disabled
Heating
Disabled
PILOT
HP
DUTY
24 VA
NA
125 VA
¼
125 VA
¼
125 VA
¼
5