B. Clearances To Combustibles
A
Parallel
Installation
A
Back Wall To Unit Hopper
Side Wall To Unit
B
Back Wall To Flue Connector
C
D
Side Wall To Flue Connector
C. Floor Protection Requirements
G
10
Do Not Burn Wet Coal!
C
D
B
Inches
Millimeters
2
51
24
610
17
432
34
864
J
G
H
Super-Magnum Coal Stoker Stove
E
Corner
Installation
E
Walls to Unit Body
Walls to Flue Connector
F
Floor protection must be of a non-combustible materi-
al. It must be located under the appliance and extend
beyond the appliance according to the measure-
ments below. Floor protection must also extend under
any horizontal sections of chimney connector and 2"
(50.8mm) beyond each side of the connector.
DANGER: The appliance legs may not be removed
for installation.
Minimum Size floor protection is 49½" Deep By 42¾"
Wide.

Floor Protection

Requirements
G
Sides
Front- measured from glass
H
Rear
J
F
E
Inches
Millimeters
15
381
24
610
Inches
Millimeters
8
203
18
457
12
305
3-90-02702R4_08/12