Clearances To Combustibles - Harman Oakleaf Wood Stove Owner's Manual

Oakleaf wood stove
Table of Contents

Advertisement

B. Clearances To Combustibles
Location
A
Unit to Side wall
B
Unit to Back wall
C
Vent Pipe to Side wall
D*
Vent Pipe to Back wall
C
For clearance reduction methods, refer to NFPA 211 or Local Codes
Location
A
Unit to Side wall
B
Unit to Back wall
C
Vent Pipe to Side wall
D*
Vent Pipe to Back wall
E*
Vent Pipe to Ceiling
F
Minimum Vertical
F
10
Dry Seasoned Wood Only!
CLEARANCE TO COmBUSTIBLES: Vertical Venting Configuration
17" / 432 mm
14" / 356 mm
26.75" / 679 mm
*17.5" / 444 mm
*D
A
CLEARANCE TO COMBUSTIBLES: Vertical Vent, Horizontal Exit
16" / 407 mm
13" / 330 mm
25.25" / 641 mm
*17" / 432 mm
*16" / 407 mm
0" / 0 mm
E
C
A
Harman® • Oakleaf Owner's Manual_R11 • 2013 -___ • 09/13
Pipe clearance may be reduced using double wall
or insulated connector pipe, provided that you
adhere to the specified clearances from the stove
itself. Follow pipe manufacturer's guidelines.
* NFPA 211 specifies 18" clearance to single wall
connector pipe. This lower clearance is based on
actual safety test conditions.
B
Pipe clearance may be reduced using double wall
or insulated connector pipe, provided that you
adhere to the specified clearances from the stove
itself. Follow pipe manufacturer's guidelines.
* NFPA 211 specifies 18" clearance to single wall
connector pipe. This lower clearance is based on
actual safety test conditions.
C
A
Oakleaf Woodburning Stove
E
D
B
3-90-798