Backward Compatibility; Package: Bis600Stateconversion.msi; Package: Languagedependentcommand.msi; Purpose | En - Bosch FPA-5000 User Manual

Fsm-5000-opc
Hide thumbs Also See for FPA-5000:
Table of Contents

Advertisement

FPA-5000 OPC-Server
3.
4.
5.
6.
7.
8.
9.
Client side PC
On the PC running the FSM-5000-OPC client software connect to the server with the same
logon you used to start the service. This also applies if you install both on the same PC. The
OPC server installation routine installs the service for the local system account by default.
Change the service to "MgtS-Service" when you use the OPC server with BIS.
3.3

Backward Compatibility

There are two setup packages to provide backward compatibility.
To install the respective file
1.
2.
Notice!
Only use these packages if you require compatibility with solutions designed for versions
prior to version 1.1 of FSM-5000-OPC server.
3.3.1

Package: BIS600StateConversion.msi

Description: States of the OPC server mapped to an offset of 600 instead of line status
designed for backward compatibility of OPC Server version 1.1 with older clients. For instance
configurations read by BIS 1.0.x requires it in order to work with the 1.1.x OPC Server.
Precondition: OPC Server ≥ 1.1.x installed.
Postcondition: Registry entry for OPC configuration set.
3.3.2

Package: LanguageDependentCommand.msi

Description: The commands are language dependent like OPC Server 1.0.x. Designed for
backward compatibility of OPC Server version 1.1 with older clients. For instance
configurations read by BIS 1.0.x requires it in order to work with the 1.1.x OPC Server.
Precondition: OPC Server ≥ 1.1.x installed
Postcondition: Registry entry for OPC configuration set.
Bosch Sicherheitssysteme GmbH
Select on the right side: Network access: Sharing and security model for local accounts.
Right click on this selection to open Properties and choose Classic– local users
authenticate as themselves.
Close all windows and restart the PC.
Open dcomcnfg and go to services (Local).
Select FPA5000OPCServer - Properties and open the Log-On tab
Choose radio button This Account – User: MgtS-Service and the password.
You are requested to restart the service in order to activate the changes. Select Stop and
Start (or Restart).
Go to the Compatibility folder on the setup disk
Double click the respective msi-file
User Guide
Installation | en
9
2013/05 | 2.0 | F.01U.261.550

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fsm-5000-opc