FPA-5000 OPC-Server
4.2
Panel Controller MPC-xxxx-B or MPC-xxxx-C
1.
2.
4.3
PC/Server
1.
2.
Bosch Sicherheitssysteme GmbH
Insert the ADC-5000-OPC card into one of the vacant address card slots.
Go to the node that has been assigned an IP address and connect the Cat.-5 cable to the
MPC‑xxxx‑B or MPC‑xxxx‑C "Ethernet" port (RJ45).
Connect the Cat.-5 cable to the PC Ethernet port. Afterwards open the DOS command
window and successfully "ping" the panel controller.
Right click on the OPC icon in the taskbar notification area and open the Connection
dialog. A list with all identified panels and their respective connection status is displayed.
If the configuration was successful, all panels which are assigned to the OPC server
should have the status "connected".
You can also find these information in a log file, located on C:\Program Files\Bosch
\FPA5000 OPC-Server\Log (for Windows XP, might be slightly different for other
operating systems).
User Guide
Step-by-Step Configuration | en
2013/05 | 2.0 | F.01U.261.550