en | Troubleshooting
5

Troubleshooting

If the configuration of the FSM-5000-OPC server doesn't work with the FPA-5000 network try
the following:
2013/05 | 2.0 | F.01U.261.550
Confirm on the panel controller that the IP address is assigned and "ping" the OPC
server.
If the Ping request is answered but the configuration still doesn't work please check
all settings on the panel,
all settings in the FSM-5000-OPC Configuration Editor,
the Ethernet adapter settings in the Window's System Configuration.
De-activate firewall
Follow these steps:
Stop OPC (see "Service" tab in Configuration Editor)
Delete bin file(s) under C:\MPOPCServer\Repository
Start OPC → A new file per node will be created.
If no elements are shown, check whether the Repository folder exists and whether it
contains a bin file for each node. The files are located under C:\MPOPCServer\Repository.
On the MPC panel controller go to Diagnostics – Network – Routing table.
A table with routing information is displayed. All networked nodes that can be reached via
the panel and that are recognized within the system network are displayed under Node.
Aside the respective interfaces via which the connected network nodes are connected to
the panel are displayed. If the OPC server configuration is correct there must be an entry
under Node with the RSN of the OPC server node and the interface "UDP tunnel".
Make sure that the panel controller does not show any troubles which could concern the
OPC server node or the network communication in general.
Verify that OPC card is detected by panel:
Choose in the start menu of the panel controller: Diagnostics - Hardware - Address cards