Alternate Floor Protection Calculation - Quadra-Fire VOYAGEUR GRAND INSERT GRAND-MBK-AU Owner's Manual

Automatic combustion control (acc)
Table of Contents

Advertisement

Voyageur Grand
B. Clearances to Combustibles (Cont'd)
2 - 15mm layers of compressed
cement sheets with a thermal
conductivity of 0.5 W/m˚K.
127mm or more from bottom of
unit, ember protection only
Figure 14.1
NOTE: Hearth Rug may be used in Suggested Area
WARNING
Fire Risk
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having juris-
diction
Quadra-fire Voyageur Grand ACC does not require a
insulating Floor Protector, as they are tested and comply
with the minimum Floor Protector requirements
of AS/NZS 2918:2001.
NOTE: HEAT SHIELD REQUIREMENTS FOR HEAT SENSITIVE WALLS. Clearances may be reduced by provision of
an appropriately located heat shield refer to AS/NZS 2198:2001 3.2.3
Page 18
required
NOTE: Keep Ashlip
Clear of Ashes
Figure 14.2
C. Minimum Opening for Masonry & Factory
Built Fireplaces
B
Location
A
Rear Width
B
Depth
C
Height
D
Front Width
*You will need to add additional clearances to these
dimensions for your specific installation. Also allow suf-
ficient clearance if you are installing an outside air kit.
Figure 14.3
7075-205
C
A
D
Millimeters
610
457
610
835
April 29, 2013